MINIMUM CLEARANCES 
 
NOTE: These boilers are intended to be installed in a room which is large compared to the size of 
the boiler. They are not intended for alcove installation and are suitable for installation on non-
combustible flooring only. 
 
 
 
 
 
 
 
DIMENSION 
D-SERIES F-SERIES
1
 
CL-SERIES 
K-SERIES 
RV, RW & AB SERIES 
 
WATER/
STEAM 
TO 50# 
STEAM 
OVER 
50# 
WATER 
/STEAM 
TO 50# 
STEAM 
OVER 
50# 
WATER 
/STEAM 
TO 50# 
STEAM 
OVER 
50# 
WATER 
/STEAM 
TO 50# 
STEAM 
OVER 
50# 
WATER 
/STEAM 
TO 50# 
STEAM 
OVER 
50# 
A 18" 
36" 
18" 
48" 
24" 
24" 
18" 
36" 
24" 
24" 
B 24" 
24" 
48" 
96" 
48" 
36" 
48" 
24" 
48" 
48" 
C
V
 & C
H
 18" 36" 18" 36" 24" 24" 24" 24" 24"  24" 
D 48" 
96" 
18" 
36" 
24" 
24" 
24" 
24" 
24" 
24" 
E
L
 & E
R
 24" 24" 18" 36" 24" 24" 24" 24" 32" 32" 
1 - F-Series boilers are approved for installation on combustible flooring. Do not install on carpeting. 
 
 
A - Clearance above boiler 
 
 
 
 
 
B - Front of boiler 
 
 
 
 
 
 
C
V
 - Clearance from gas vent, measured vertically above pipe 
 
C
H
 - Clearance from gas vent, measured horizontally or below pipe 
 
D - From back of boiler 
 
E
L
 - Left side of boiler 
 
E
R
 - Right side of boiler 
 
These clearances are general minimum clearances. Local codes may dictate larger clearances.