Bryant LEGACY LINE 580J Manual De Usuario

Descargar
Página de 86
47
Table 31 – COOLING CAPACITIES
2--STAGE COOLING (RTPF ONLY)
12.5 TONS
580J14 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE
TEMP (F) AIR ENT
CONDENSER (Edb)
AIR ENTERING EVAPORATOR --- CFM
3750/0.02
5000/0.06
6250/0.05
Air Entering Evaporator --- Ewb (F)
72
67
62
72
67
62
72
67
62
75
TC
183.66
166.86
151.43
194.90
177.83
162.05
201.97
184.84
170.53
SHC
79.39
100.52
121.91
91.70
119.42
147.05
102.94
137.00
166.71
kW
9.82
9.63
9.46
9.58
9.76
9.96
10.04
9.84
9.67
85
TC
172.71
156.78
142.09
183.32
167.13
152.17
189.98
173.73
160.25
SHC
69.03
90.92
112.95
80.69
109.17
137.51
91.49
126.33
156.65
kW
10.82
10.63
10.45
10.57
10.76
10.96
11.04
10.84
10.67
95
TC
161.37
146.24
132.38
171.36
156.04
141.86
177.62
162.22
149.50
SHC
58.44
81.04
103.77
69.42
98.67
127.71
79.83
115.45
146.15
kW
11.92
11.73
11.56
11.68
11.86
12.05
12.14
11.93
11.77
105
TC
149.57
135.32
122.21
158.89
144.45
131.10
164.74
150.27
138.35
SHC
47.57
70.92
94.32
57.85
87.91
117.61
67.79
104.26
135.30
kW
13.12
12.94
12.77
12.89
13.06
13.24
13.32
13.13
12.97
115
TC
137.22
123.88
111.55
145.85
132.33
119.84
151.27
137.71
126.67
SHC
36.31
60.47
84.57
45.87
76.77
107.19
55.34
92.66
123.98
kW
14.41
14.25
14.10
14.20
14.35
14.53
14.59
14.42
14.28
580J14 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE
TEMP (F)AIR ENT
CONDENSER(Edb)
AIR ENTERING EVAPORATOR --- Ewb (F)
75 Dry Bulb
62.5 Wet Bulb
(50% Relative)
75 Dry Bulb
64 Wet Bulb
(56% Relative)
75 Dry Bulb
65.3 Wet Bulb
(60% Relative)
Air Entering Evaporator --- Cfm
3750
5000
6250
3750
5000
6250
3750
5000
6250
80
TC
52.42
45.88
36.99
62.64
58.07
51.07
71.56
68.64
63.23
SHC
---0.39
---0.54
---0.67
---0.31
---0.46
---0.58
---0.26
---0.40
---0.52
kW
9.65
9.39
9.07
9.97
9.77
9.50
10.25
10.11
9.89
75
TC
53.45
46.63
36.10
63.77
59.11
51.87
72.76
69.80
64.31
SHC
0.59
0.44
0.30
0.67
0.52
0.40
0.72
0.58
0.47
kW
9.09
8.83
8.49
9.39
9.20
8.94
9.67
9.53
9.32
70
TC
54.33
46.91
37.58
64.77
60.01
52.30
73.80
70.80
65.24
SHC
1.56
1.41
1.29
1.64
1.50
1.38
1.70
1.56
1.45
kW
8.81
8.53
8.62
9.15
8.94
8.65
9.46
9.31
9.08
60
TC
55.47
49.48
40.48
66.62
62.07
54.88
75.68
72.76
67.28
SHC
3.50
3.38
3.27
3.59
3.47
3.36
3.65
3.52
3.42
kW
8.36
8.84
8.98
9.88
9.56
9.10
9.83
9.64
9.31
50
TC
58.33
51.72
42.81
68.72
63.93
55.84
77.74
74.77
69.24
SHC
5.47
5.35
5.24
5.54
5.43
5.32
5.60
5.49
5.39
kW
8.98
9.25
9.43
9.33
8.97
8.73
9.55
9.33
9.70
40
TC
60.33
53.69
46.89
70.67
65.93
49.83
79.46
76.62
71.24
SHC
7.42
7.31
7.22
7.49
7.39
7.23
7.55
7.45
7.37
kW
9.16
9.88
9.06
9.50
9.05
9.47
10.31
10.00
9.48
NOTE: Perfect Humidity only available on 2---stage RTPF models.
LEGEND
Edb 
--- Entering Dry---Bulb
Ewb --- Entering Wet---Bulb
kW
--- Compressor Motor Power Input
Idb
--- Leaving Dry---Bulb
Iwb --- Leaving Wet---Bulb
SHC --- Sensible Heat Capacity (1000 Btuh) Gross
TC
--- Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t
ldb
= t
edb
sensible capacity (Btuh)
1.10 x cfm
t
lwb
= Wet---bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h
lwb
)
h
lwb
= h
ewb
total capacity (Btuh)
4.5 x cfm
Where: h
ewb
= Enthalpy of air entering evaporator coil
580J