Bacharach GDC-150 Manual De Propietario

Descargar
Página de 28
GDC-150 Operation Manual 
 
 
10 
 
5209-9000 Rev 0 
After installation, simply locate the lid hinges over the installed base hinges and pull 
toward you.  The hinges should easily “snap” back into place. 
 
By design, the overlapping door of the PVC enclosure makes it inherently drip proof, 
although it is not water tight or dust tight.  The optional water-tight enclosure has four 
screws for sealing the door to the base.  Refer to Figure 1-2 on page 2. 
 
3.3.  Sensor Mounting Height Recommendations 
 
Some toxic gases such as ammonia (NH
3
) and combustible gases such as methane 
(CH
4
)  are lighter than air, therefore the sensor/transmitter should be installed on or 
near the ceiling. 
 
Some toxic gases such as carbon monoxide are only slightly lighter than air, therefore 
the sensor/transmitter should be installed at approximately 4’ to 6’ from the floor. 
 
Oxygen sensors should be installed at approximately 4’ to 6’ from the floor. 
 
For toxic gases, combustible gases, and vapors  that are heavier than air,  the 
sensor/transmitter should be installed with the sensor opening at 6” from the floor. 
 
Although most refrigerants (e.g., Freons) are heavier than air, some applications may 
be better suited to a slightly higher mounting height for refrigerant sensors. 
 
 
 
NOTE:  If the area to be monitored is a wet environment, water-tight 
enclosures should be used.  The water-tight enclosure must be installed 
using the indicated holes or it may leak.  Damage caused by leaking 
because of improperly installed enclosures is not covered under 
warranty.  If the area to be monitored has the potential for water spray, a 
splash guard should be used to protect the sensor. 
 
 
 
3.4.  Wiring the GDC-150 for Power 
 
If powering the  GDC-150  with 24 VAC,  use  terminals  1  and  2.    If powering the 
GDC-150 with 24 VDC, the positive (red) wire should be connected to terminal 2 and 
the negative (black) wire should be connected to terminal 3.  The signal wire is always 
connected to terminal  4.  See  Figure  3-4  for proper wiring examples and  Figure  3-5 
for improper wiring examples. 
 
Terminals  5, 6, and 7  are used only if the relay  option has been supplied.  Double 
check the relay ratings in the specifications section of this manual before operation.  
For normal operation, the relay control wiring should be connected to N/C  and COM 
(fail-safe operation is used).