GDC-150 Operation Manual 
 
 
14 
 
5209-9000 Rev 0 
 
4.2.  Detecting Gas 
 
Upon detection of the presence of target gas, the signal output increases to a value 
equal to the amount of gas being detected by the sensor.  If the LED display option 
has been supplied, this value will be displayed.  If the concentration of gas is above 
the preset  alarm threshold, the outer LED changes to red, the alarm relay de-
energizes and the amber relay coil LED goes out.   
 
As the detected gas level subsides, the output signal will decrease again to a value 
equal to anything being detected by the sensor and this will be indicated on the LED 
display (if this option has been selected).  The relay will automatically reset after the 
signal drops below the set point value. 
 
4.3.  System Failure 
 
In the event of a system failure, the outer LED will flash red, the relay will de-energize, 
the relay coil LED will go out and the output signal will drop below 4.0 mA.  A failure 
can consist of a burned out sensor element (solid-state or catalytic), a failed or 
damaged component on the circuit board, or a wiring-related problem. 
 
4.4.  Sensor Notes 
 
Sensor Type
Operation Notes
 
 
Solid-State 
(Refrigerant)
 
•  Not gas specific 
•  Respond to a fairly wide range of interfering gases and 
vapors 
• 
Temperature and humidity compensated to reduce drift in 
environments where these values change regularly
 
Solid-State 
(Combustible)
 
•  Not gas specific, but are less likely to suffer from false 
alarms from interfering gases (due to the extremely high 
measuring range for which they have been calibrated) 
Catalytic 
(Combustible)
 
•  Specific to combustible gases and vapors 
•  Temperature compensated 
Electrochemical 
(E.g., Oxygen)
 
•  These sensors are quite gas specific 
•  Will respond to some other gases (see cross sensitive 
gases table on page 7 for more information) 
•  Temperature compensation to reduce drift in environments 
where the temperature changes regularly 
 
 
                                                 
10
  
Sensors require lengthy warm up and stabilization time after installation.  Do not 
perform any calibration functions until the sensors have been operating for at least 24 
hours.