Single Zone Gas Monitor 
P/N: 3015-4256 Rev 13 
9 
2.3.2.  Tubing Considerations 
Use  ¼  in.  outside diameter (0.040  in.  wall) flex tubing for all air lines (P/N 0304-2743  or equivalent  for 
HGM; P/N 0304-2742 or equivalent for AGM). The tubing should be clean and free of moisture or other 
contaminants. The tubing should be cut cleanly with a sharp knife and care should be taken not to distort 
the tubing end. 
 
IMPORTANT!  Due to the reactive nature of refrigerant and ammonia gasses, it is 
important to use materials that will not absorb the gas as it passes through the sampling 
system. The use of unauthorized tubing or any other materials in the gas-sampling stream 
may lead to erroneously low readings. 
 
All tubing bends should have a radius of no less than 5"  (127 mm)  to  ensure  proper airflow. If kinks or 
obstructions occur in the line, the monitor may not function properly.  
2.3.3.  Connecting the Gas Sample Line 
Please refer to  the section  titled  Suggested Location of Sampling Point  (page  4) to learn more about 
where to take a gas sample. 
The gas-sample line can be up to 500 ft (152.4 m) in length. The combined length of the sample line and 
exhaust line (if one is used) should not exceed 500 ft (152.4 m). The end of this line should be placed near 
the potential leak source and positioned to reduce the possibility of mists, aerosols, oil, water, dust, or other 
contaminates from being drawn into the monitor. For added protection, a termination filter (P/N 3015-3420) 
supplied with the monitor must be attached to the end of this line.  
 
CAUTION:  The introduction of contaminants through the gas-sample line can result in 
serious and permanent damage to the monitor. 
 
Depending on type of use and location of lines, the optional end-of-line water stop filter assembly can be 
used to prohibit moisture from entering the intake lines.  Place the end of the intake line into the blue 
receiver of the end-of-line water stop and tighten sufficiently. 
 
NOTE:  Only one filter assembly, either the line-end filter or end-of-line water stop, should 
be used for each line. 
 
 
The Single Zone monitor uses push-to-
connect (PTC) style connectors. 
 
To insert sample lines, firmly push the 
appropriate tubing into the hole in the 
center of the connector until it seats in 
the connector.  Refer to the figures at 
the left. 
 
To remove tubing from a PTC 
connector, push  and hold  the spring-
loaded 
collar 
inwards, 
then 
simultaneously  withdraw  the  tubing.  
Refer to the figures at the right. 
 
Figure 2-3.  Using PTC Connectors: Connecting (Left) and Disconnecting (Right)