Bacharach GDA-1600 Manual De Propietario

Descargar
Página de 54
Instruction 5700-9001 
 
GDA-1600 16-Channel Controller 
15 
Entries 
Description 
Sensor Direct 
with Local Cal 
Sensor Direct is identical to Analog with Local Cal and both activate the GDA-1600’s 
Cal Mode features (see section 3.2.7 on page 19).  Problems may arise if calibrations 
are performed in two places upon the same signal so that Cal Mode menus become 
visible only when Sensor Direct  or  Analog with Local Cal  is selected.  These 
selections should only be used when the input originates from a non-calibrated 
signal source such as the Bridge Sensor Input option described in section 4.2.3 (page 
31), or, our GDX-150 Transmitter with a non-calibrated 4-20mA output.  These 
applications require the GDA-1600 to be used as the calibration point since the 
sensors have no zero or span controls. 
12-bit analog inputs may be direct from Sensor Input options of Voltage/Current 
Input options. 
Analog Input 
with Local Cal 
Analog with Local Cal is available when the GDA-1600 will be the point of calibration 
for the analog input.   
Analog Input 
Analog Input should be selected when the channel’s input comes from a transmitter 
or monitoring device with a calibrated output such as 4-20mA.   
Modbus 16 Bit 
The  Modbus  16 Bit  menu may be used with most wireless modems if a wireless 
Modbus interface is required.  Modbus 16 Bit is returned as an integer that can be 0 
to 65536.  Typically, a slave will put out a number with say 10bit (0-1023) or 12bit (0-
4095) resolution to represent a range value.  In the GDX-350, this value is 12 bit and 
is ranged in a 4-20 mA style signal where 4mA sends a value or counts of 800 (min 
raw) and 20mA sends a value or counts of 4000 (max raw).  A slave with a 10-bit 
output would send 200 for 4mA and 1000 for 20mA. 
The Modbus Master RS-485 port supports most integer types, resolutions, and 
formats.  “MODBUS 16 BIT” menu indicates that 16-bit is the maximum
MB 16 Bit 
Signed 
, but also 
supports 8-, 10-, and 12-bit formats by editing the Min/Max Raw menus to contain 
the correct counts ranges. 
Modbus 16 Bit Signed sends 15 data bits and the MSB indicates the sign bit.  If the 
bit is set, the value is negative and positive if not set.  In this case, the min raw is 
usually zero and the max raw is set to the full scale value. 
Wireless RF900  The Wireless RF900 input option should only be used with our proprietary wireless 
monitors. 
Modbus 32 Bit 
Modbus 32 Bit represents a IEEE754 data format that requires no scaling between 
min raw and max raw values.   The value is read directly by the firmware and is 
displayed in the format sent by the slave. 
NOTE:  Most slaves do not implement a means to determine if the value is valid or 
faulty.  Generally, they return a zero value with a fault present (requiring additional 
data registers be read to determine the validity of the data).  There is no standard 
defining how this is done, so this option typically requires special firmware drivers.  
(Compare this to 16-bit data types, in which the value is driven negative below the 
controller’s fault level which generates a fault alarm trip.  This, along with expected 
cal data values can be achieved by reading a single register.)