Brocade Communications Systems Brocade MLX Series and Brocade Netlron XMR 53-1002373-02 Manual De Usuario

Descargar
Página de 452
Brocade MLX Series and Brocade NetIron XMR Hardware Installation Guide
355
53-1002373-02
Replacing a power supply
8
NOTE
A threshold value of 0 will not automatically shutdown a power supply due to failures.
For Syslog messages, please refer to Appendix A, Using Syslog in the Brocade MLX Series and 
Brocade NetIron Family Configuration Guide
.
Clearing power supply failure timestamps
Use the power-supply monitoring clear command to clear all collected failure timestamps for a 
given power supply, or for all available power supplies.
To clear all collected failure timestamps for a power supply, enter the following command.
Brocade(config)# power-supply monitoring clear 1
This will clear all collected failure timestamps for the Power Supply # 1
Are you sure? (enter 'y' or 'n'): y
To clear all collected failure timestamps for all available power supplies, enter the following 
command.
Brocade(config)# power-supply monitoring clear all
This will clear all collected failure timestamps for all available Power Supplies
Are you sure? (enter 'y' or 'n'): y
You are asked to verify this command by entering “yes” or “no.
Syntax: power-supply monitoring clear <decimal | all>]
By default, no power-supply monitoring is configured.
The <decimal> variable specifies a power supply number, The all keyword clears all available power 
supplies.
Displaying power supply monitoring timestamps
To display timestamps for failures on any power supply, enter the following command.
Brocade# show power-supply-monitoring
PS-1     PS-2     PS-3     PS-4     PS-5     PS-6     PS-7     PS-8
1 ) 0        0        0        0        0        0        0        0
2 ) 0        0        0        0        0        0        0        0
3 ) 0        0        0        0        0        0        0        0
4 ) 0        0        0        0        0        0        0        0
5 ) 0        0        0        0        0        0        0        0
6 ) 0        0        0        0        0        0        0        0
7 ) 0        0        0        0        0        0        0        0
8 ) 0        0        0        0        0        0        0        0
9 ) 0        0        0        0        0        0        0        0
 
The show power-supply-monitoring command displays the last 32 recorded failure timestamps for 
a power supply. The current configured power supply monitoring threshold value is also displayed 
at the end of the output.
Syntax: show power-supply-monitoring