Safety Circuit Voltage Trace 
Note: This procedure assumes a cold tank. 
Step 1. 
Remove three screws (Phillips screw driver) from 
control access cover on blower and remove
cover.
Safety Circuit Voltage Trace 
WARNING
115 volt potential exposure. Use caution making voltage checks to avoid 
personal injury.
Control access 
cover
Position gas control switch to the “ON” 
position and adjust the thermostat dial 
to call for heat. Is there 10 to 13VAC 
between the red wire leading to the 
blower temperature switch and the 
green ground wire? Blower must be 
running during this voltage check (see 
photo 15). 
Is LED on gas valve flash-
ing the “heartbeat” code 
(alternating bright/dim)? 
No voltage from gas control. 
Call for technical support. 
Verify 115VAC to gas con-
trol (see page 41). 
Is there 10 to 13VAC between 
the yellow wire leading from the
pressure switch and the green 
ground wire (see photo 27)? 
Is there continuity through 
the blower temperature 
switch (see page 31)? 
Check for loose or broken 
wire connection at switch 
terminals.
Do you hear or can you 
see the igniter sparking? 
Check igniter/sensor (see page 
22). Is igniter/sensor OK? 
Correct igniter/
sensor problem 
Determine cause of blower 
temperature switch activa-
tion and correct.  
Faulty cord set 
or gas control
Safety circuit
voltage is OK.  
If burner does not light, ob-
serve LED flash code on gas 
control and refer to trouble-
shooting section on page 17. 
Green ground wire 
Red sire leading to 
blower temp. switch 
Yellow wire leading
from pressure switch 
15
14
N
N
Y
Y
N
Y
N
Y
N Y 
Y