Bradford-White Corp EFR160T120 Manual De Usuario

Descargar
Página de 72
 
 
20
 
VENTING 
The venting instructions must be followed to avoid restricted combustion or recirculation of flue gases.  Such conditions 
cause sooting or risks of fire and asphyxiation. 
 
This water heater can be installed as either a direct vent system or power vent (air from inside) system.  If it is installed as a 
direct vent system, then the air intake and the exhaust vent are piped to the outside.  If a power vented system is used, then air 
is drawn from inside and only the exhaust is piped to the outside.  Determine which system is best for your application and 
install as described in the following sections. 
 
DIRECT VENT INSTALLATION 
Venting may be run horizontally through an outside wall or vertically through a roof through using either 2 inch (5.1 cm), 3 
inch (7.6 cm), or 4 inch (10.2 cm) diameter PVC, ABS or CPVC pipe.  This water heater is supplied with a screened intake 
and exhaust elbow referred to as the air intake terminal and the exhaust vent terminal.   
 
NOTICE
 
If 4 inch (10.2 cm) PVC, ABS, or CPVC pipe is used, then a use a 4 inch (10.2 cm) to 2 inch (7.6 cm) reducer 
fitting before exiting the wall or roof to use the supplied screened intake and exhaust terminals. 
If 3 inch (5.1 cm) PVC, ABS, or CPVC pipe is used, then use a 3 inch (5.1 cm) to 2 inch (7.6 cm) reducer fitting 
before exiting the wall or roof to use the supplied screened intake and exhaust terminals. 
 
Direct Vent Terminal Location 
Plan the vent system layout so that proper clearances are maintained from plumbing and wiring.  Before the vent is installed, 
determine the vent pipe termination location as shown in Figure 12. 
 
NOTICE
 
The air intake and exhaust terminals may be located on separate outside walls or one terminal may exit the roof 
while the other is through the wall. The total combined equivalent vent length must be within the limits specified 
in the venting tables and the intake length cannot exceed the exhaust by more than 30 feet (9 m). The minimum 
recommended vent separation distance between the intake and exhaust terminals is 36 inches (91.4 cm). Local 
conditions may require a need for greater vent separation distances.