Power Supply
Dedicated 120 VAC, 60 Hz., 15 A
Current Draw 
Less than 5 Amps.
Approved Gas Type
 Natural or Propane.  Gas supply must match the gas type listed on the water
 heater rating label.
Gas Supply Connection  
  1" NPT connection to gas valve for 370,000 Btu/hr. and over for natural gas,
 ¾" NPT for rest. Schedule 40 black iron pipe recommended.
Gas Pressure (Nat. & L.P.)
 Manifold Pressure: 4.5" w.c. natural gas, 10.0" w.c. L.P. Gas Supply
 Pressure: At least 1" above manifold pressure with water heater operating,
 14" w.c. maximum.
Venting System
Atmospherically Vented, Type B venting system or approved chimney.  Follow
 current National Fuel Gas Code requirements or in Canada, the Natural Gas
 and Propane Installation Code.
Minimum Clearance for Servicing  
24" Front Clearance, 20" Top, 6" Sides.
Maximum Water Supply Pressure
 150 PSI.
Thermostat Sensor(s)
 Redundant thermister with 11,900 + or - 0.5% ohms resistance at 70 deg. F.
Sensor inside well for lower sensor.  Some models use an additional upper
sensor (w/o well) with same resistance values.
Control Board
Honeywell Integrated Control Board for Temperature Control, Flue Damper,
 and Ignition Control Functions.  Operates on 24 volts AC current from
 transformer. Some models use single sensor boards, others use two
 sensors.
Control Display
Honeywell LCD Control Display with Temperature Setpoint, Format, and Error
 Code Display in User Mode, Diagnostic Functions in Service Mode.
 Communicates with Control Board.
Transformer
120 VAC Primary, 24 VAC Secondary, 40 VA.
Pilot
Intermittent Pilot with Spark Electrode and Flame Sensor monitored by Control
Board.
Flue Damper
 24 VAC, 60 Hz., 80 Ma.
Page 5
Specifications