Bradford-White Corp BWCV Manual De Usuario

Descargar
Página de 44
Internet Version for Reference Only
 
Bradford White
Page 6
Copper Brute II
Page 7
                                     Required                 Recommended
    Appliance            Clearance From            Service Access
      Surface          Combustible Material            Clearance
                               inches         
cm              inches         cm
     Left Side                1             
2.5                 24             61
    Right Side               1             
2.5                 24             61
         Top                    1             
2.5                 12             30
        Back                   1             
2.5              
**
12**         
30**
        Front                   1             
2.5                 36             91
      Vertical
  (Category 1)            6*          
15.2*
        Vent
    Horizontal         per UL1738 venting
  (Category 3)         system supplier’s
        Vent                   instructions
*1" (2.5cm) when b-vent is used.
**When vent and/or combustion air connects to the back, 
recommended clearance is 36" (91cm).
Table 2. Clearances.
1.6  Locating Pump-Mounted Water Heater 
with Respect to Storage Tank(s)
For best results, a pump-mounted water heater 
should be located within 15 feet (4.6m) of the storage 
tank(s). The pump is sized for 30 feet (9.1m) of piping.
If the heater must be installed with longer piping 
runs, then larger diameter pipe or tubing shall be used. 
Consult the factory for assistance.
1.7  Locating Appliance for Correct 
Horizontal Vent/Ducted Air Distance 
From Outside Wall
The forced draft combustion air blower/blowers 
in the appliance has/have sufficient power to pull air 
and vent properly when the following guidelines for 
horizontal air and vent are followed (see Table 1).
NOTE: On models 750-2000, the vent collar size is 
larger than the size of the vent pipe that can be used. 
Vent collar size and horizontal pipe diameters can 
be found in Table 1. The larger vent collar size is to 
accommodate Category I (vertical) vent systems.
NOTE: When located on the same wall, the 
combustion air intake terminal must be installed 
a minimum of 12" (30cm) below the exhaust vent 
terminal and separated by a minimum of 36 inches 
(91cm) horizontally.
The air intake terminal must be installed high 
enough to avoid blockage from snow, leaves and other 
debris.
SECTION 2. 
Venting and Combustion Air
2.1  Combustion Air
Copper Brute II water heaters must have 
provisions for combustion and ventilation air in 
accordance with section 5.3, Air for Combustion and 
Ventilation, of the National Fuel Gas Code, ANSI 
Z223.1, or Sections 7.2, 7.3 or 7.4 of CSA B149.1, 
Installation Codes, or applicable provisions of the local 
building codes.
A Copper Brute II heater may receive 
combustion air from the space in which it is installed, 
or it can be ducted directly to the unit from the outside. 
Ventilation air must be provided in either case.
2.1.1  Combustion Air From Room
In the United States, the most common 
requirements specify that the space shall communicate 
with the outdoors in accordance with method 1 or 2, 
which follow. Where ducts are used, they shall be of 
the same cross-sectional area as the free area of the 
openings to which they connect.
Method 1: Two permanent openings, one 
commencing within 12 inches (30 cm) of the top 
and one commencing within 12 inches (30 cm) of 
the bottom, of the enclosure shall be provided. The 
openings shall communicate directly, or by ducts, 
with the outdoors or spaces that freely communicate 
with the outdoors. When directly communicating 
with the outdoors, or when communicating to the 
outdoors through vertical ducts, each opening shall 
have a minimum free area of 1 square inch per 4000 
Btu/hr (5.5 square cm/kW) of total input rating of all 
equipment in the enclosure. When communicating to 
                                                Horizontal          Air Collar
   Heater       Vent Collar          Vent Pipe            & Pipe           Max. Pipe           Max. No.            Side Wall              Side Wall
     Size               Size                Diameter          Diameter           Length             of Elbows               Vent                Combustion
                                                                                                                                                       Terminal             Air Terminal
                      in.      
cm            in.       cm           in      cm          ft.      m                                     Part Number        Part Number
     500            6       
15            6        15             6      15           50    15                    3                 CA001401            20260701
     750            8       
20            6        15             6      15           50    15                    3                 CA001401            20260701
    1000          10      
25            8        20             8      20           50    15                    3                 CA001402            20260703
    1250          12      
30            8        20             8      20           50    15                    3                 CA001403            20260703
    1500          12      
30            8        20             8      20           50    15                    3                 CA001403            20260703
    1750          14      
36            8        20             8      20           50    15                    3                 CA001403            20260703
    2000          14      
36           12       30            12     30           50    15                    3                 CA001404            20260706
Table 1.  Horizontal Vent / Combustion Air Parameters.