Bradford-White Corp 500-1825 Manual De Usuario

Descargar
Página de 20
Internet Version for Reference Only
 
BRADFORD WHITE
Page 8
B4 Volume Water Heater
Page 9
Figure 9), must be piped, but not fastened, to a 
drain or floor sink. The drain pipe must be the 
same size as the valve outlet and must pitch 
downward from the valve.
         Special attention must be given to relief valve 
settings in installations where the heater is 
located on the ground floor of a tall building. The 
static pressure of the system is elevated and could 
cause the relief valve to leak. Where no special 
setting of the relief valve is ordered, the factory 
will furnish a 125 psi setting. Never reduce the 
relief valve openings.
3.      Pressure relief valve lever must be tripped at 
least once a year to insure that waterways are 
clean. When manually operating lever, water will 
discharge through drain line. Precautions must be 
taken to avoid contact with hot water and water 
damage.
4.      The weight of all water and gas piping should be 
supported by suitable hangers or floor stands.
5.      Check piping diagrams with local applicable 
plumbing, heating and building safety codes.
6.      All two-temperature systems using temperature 
valves must have forced recirculation in the low 
temperature building loop.
7.      A check valve installed at the hot water inlet to 
the tempering valve will prevent cold water from 
being drawn in reverse through the tempering 
valve into the hot water.
8.      When installing a tempering valve, place at 
bottom of antithermosyphon loop at least 24" 
high to prevent excessive hot water from entering 
mixed water supply. Bring the cold water supply 
up from the floor to the valve (see Figure 10).
2.7  Water Expansion
When cold water is heated the water expands. If 
no water is being used during the heat-up period the 
expanded water will normally back up into the city 
mains.
A water pressure reducing valve installed in the 
incoming cold water line may act as a check valve and 
prevent the expanded water from moving backward. 
This will cause pressure to rise in the heater, which 
will be relieved by the pressure relief valve.
If the relief valve pops frequently a mineral 
deposit may build up on the valve seat, causing it to 
leak.
The  following  suggestions  may  solve  the 
problem:
1.      Install a properly sized expansion tank.
2.      Replace the installed water pressure reducing valve  
with a suitable valve having a back flow port. These 
valves have a back flow port which allows water  
to flow backwards when the pressure in the system 
exceeds the pressure in the mains.
3.      Install an auxiliary small relief valve set at 25 psi 
less than the main relief valve. The valve must 
be piped to a drain and may require occasional 
cleaning. It will bleed off the expanded water 
and protect the main pressure relief valve from 
becoming fouled.
2.8  Pump Performance and Installation
1.      The factory provided pumps on all Copper Brute 
heaters are sized to provide proper circulation 
through the heater and heater-to-tank circulation 
loop (see Figures 11 and 12). If the heater-to-tank 
circulating loop does not contain more than 6 
elbows or 30 feet of pipe, use pipe fittings in the 
loop no smaller than the following:
                     Model                              Pipe Size
             500 through 850                            2"
           1010 through 1825                       2-1/2"
Figure 9. Pressure Relief Valve Location.
Pressure
Relief
Valve
Hot
Water
Hot
Water
Storage
Tank
Floor
Automatic
Tempering
Valve
Cold
Water
Tempered Water
24"
Figure 10. Tempering Valve Installation.