D9412GV2/D7412GV2 | Operation and Installation Guide | 9.0   Off-Board Points 
 
40 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
 
 
Figure 14:  Program Record Sheet 
EN | 25
bold
Point Assignments (001 through 040)
POPIT Switch
Setting
Trans-
lation
Point
#
Point
Index
Area
Assign
Debounce
BFSK/
Relay
Custom Point Text
100
001
(3)
_ _
(1)
___
(2)
_____
(1)
____
P1 FIRE
___________________
200
002
(1)
_ _
(1)
___
(2)
_____
(2)
____
P2 PANIC
___________________
300
003
(25) _ _
(1)
___
(2)
_____
(3)
____
P3 DELAY
___________________
400
004
(13) _ _
(1)
___
(2)
_____
(4)
____
P4 FOLLOW ___________________
500
005
(7)
_ _
(1)
___
(2)
_____
(5)
____
P5 INSTANT ___________________
600
006
(7)
_ _
(1)
___
(2)
_____
(6)
____
P6 INSTANT ___________________
700
007
(7)
_ _
(1)
___
(2)
_____
(7)
____
P7 INSTANT ___________________
800
008
(7)
_ _
(1)
___
(2)
_____
(8)
____
P8 INSTANT ___________________
0 1 2 3 4 5 6
101
009
__ __
(1)
___
(2)
_____
(1)
____
P9
___________________
Default values are shown in ( ) or in bold
D9412GV2/D7412GV2 | Program Record Sheet | RADXPNTS Handler
 
 
9.3.8 POPIT 
Labels 
D9412GV2 off-board points are numbered 9 to 127 
and 129 to 247. The D7412GV2 uses Points 9 to 75 
only. The D9412GV2 reserves Points 128 and 248 for 
internal use. POPITs must be connected for Points 129 
to 247 to expansion loops connected to POPEX #2.  
Two sheets of peel-off POPIT labels are supplied with 
the D8125 POPEX Module. Use the sheet marked 
“Bank1” for Points 9 to 127. Use the sheet marked 
“Bank2” for Points 129 to 247. 
Each label has two parts. Place the smaller part (with 
only the point number) on the chip. Place the larger 
part (with the switch settings) on the base of the 
POPIT. Set the switches and cover the POPIT.  
Do 
not program two POPITs for the same point 
number. After programming all the points, perform a 
Service Walk Test. The D9412GV2/D7412GV2/ 
D7212GV2 Installation and Troubleshooting Quick Reference 
Guide
 (P/N: F01U003638) contains instructions for 
performing a Service Walk Test. If a point does not 
test, check the programming for a duplicated address. 
Walk Test and Service Walk Test Do Not Show 
Extra Points: If the point assignment switches on a 
POPIT or OctoPOPIT are set incorrectly, it can create 
both missing and extra points. If the same point 
number is assigned to two or more POPITs or 
OctoPOPITs, none of the points with that number test 
correctly. Refer to Section 9.1 Point (Zonex) Bus: 
D9412GV2 Terminals and D7412GV2 Terminals 
on page 
34. 
9.4 
D8128D OctoPOPIT Module 
 
 
Modules D8128, D8128A, or D8128B are 
incompatible with the D9412GV2 or 
D7412GV2. Use only the D8128D 
OctoPOPIT Module. Using Modules D8128, 
D8128A, or D8128B can cause intermittent 
Missing and Restoral Reports. 
9.4.1 Description 
The D8128D OctoPOPIT Module combines the 
functions of the D8125 POPEX Module and the 
D8127/D9127 POPIT Modules to provide eight off-
board points in a single module. You can wire both 
D8128D OctoPOPIT and D8125 POPEX Modules in 
parallel to the Zonex Bus terminals on the same control 
panel. 
Review Section 6.0 Power Outputs on page 25 to ensure 
there is enough power for the OctoPOPITs and other 
powered devices that will be connected to the system. 
Up to thirty D8128D Modules can be connected to the 
D9412GV2 Control Panel. A maximum of nine 
D8128Ds can be connected to the D7412GV2 Control 
Panel (three points can be used on the last 
OctoPOPIT). 
9.4.2 Listings 
The D8128D OctoPOPIT Module is UL Listed for 
Local or Police Connected Burglary Alarm, Central 
Station Burglary Alarm, Household Burglary Alarm 
applications, and commercial fire applications (UL 864 
and NFPA 72).