Two-pipe oil flow, one nozzle, low fire, “
H
” pump
• Install two high-quality shutoff valves in accessible loca-
tions on the oil supply line. Locate one valve close to the
tank. Locate the other valve close to the burner, upstream
of the fuel filter.
  Burner fuel flow
One-pipe systems
 – See 
Figure 8
 for the fuel flow paths
for high-fire and low-fire operation. Oil supply connects to
one of the fuel unit Inlet ports.
Do not
 install by-pass plug in a one-pipe
system. Could cause unit seal failure, oil
leakage and potential fire and injury hazard if
ignored.
Two-pipe systems 
– See 
Figure 9
 for the fuel flow paths
for high-fire and low-fire operation. Oil supply connects to
one of the fuel unit Inlet ports. Oil return connects to the
fuel unit Return port.
By-pass plug 
must 
be installed in a two-pipe
system. Failure to comply could cause unit
seal failure, oil leakage and potential fire and
injury hazard.
Low-fire/high-fire operation
 – The fuel unit nozzle port
pressure is factory set at 300 psig.
• At high fire, full pressure (300 psig) is applied at both
oil nozzles, causing full input.
• At low fire, full pressure (300 psig) is applied at one
nozzle, causing reduced input.
Figure 9b
Two-pipe oil flow, two nozzles, high fire, “
H
” pump
Return port
Nozzle port
Oil valves
Nozzle & adapter
Inlet port
Return line to oil tank
Air bleed valve
Legend 
(for Figures 8a, 8b, 9a and 9b)
3512
d
200 psig
to
300 psig
c
c
c
k
200 psig
to
300 psig
b
g
a
p
3513
d
200 psig
to
300 psig
c
c
c
k
200 psig
to
300 psig
200 psig
to
300 psig
b
g
a
p