Figure 8. UL gas train confi guration
MSC
U
PRSSOV
SSOV1
MLTC
U
BURNER
C6097B
HGPS
TP
C6097A
LGPS
TC
TC
MSC
SSOV1
PRSSOV
MLTC
U
U
TP
TC
TC
HGPS
LGPS
ABBREV.
HGPS
LGPS
MSC
MLTC
PRSSOV
 
SSOV1
TC
TP
U
ITEM DESCRIPTION
HIGH GAS PRESSURE SWITCH
LOW GAS PRESSURE SWITCH
MAIN SHUTOFF COCK
MAIN LEAK TEST COCK
PRESSURE REGULATING 
SAFETY SHUTOFF VALVE
SAFETY SHUTOFF VALVE #1
TEST COCK
TEST PORT
UNION
Section: Connect Gas Piping
When pressure 
reducing safety 
shutoff valves are used, the distance 
from the fi nal shutoff valve (PRSSOV 
in Fig. 8) to the burner manifold must 
be kept to a minimum for good light-off 
reliability.  R.W. Beckett recommends the 
following maximum lengths:
Pipe Size
1”
1-1/4”
1-1/2”
2”
Max. Length
12”
15”
18”
24”
If a Normally Open Vent Valve (not 
shown) is used, the distance between 
the SSOVs must be kept to a minimum 
using the shortest practical nipples.
by natural gas appliances.  It is safe and effective for 
propane usage in this design application.
Optional – Gas trains for IRI and FM are available and 
must be specifi ed when ordering a burner.  
Verify – Verify that the train components are not 
damaged and all piping and fi ttings are clean inside and 
out.  The gas train is normally shipped as components 
and must be assembled and installed at the site.  
 
Vent lines – Install vent lines to any gas valve component 
that requires atmospheric air pressure to balance a 
diaphragm.  Vent lines must be run to the outdoors, with 
the termination point away from fresh air intakes and 
windows. The terminal opening must be fi tted with a wire 
mesh screen to block insects and other contaminants 
from entering the vent and must be mounted in such a 
position that water, ice, dirt, or any other foreign matter 
cannot infi ltrate and block the vent piping. Make sure the 
fi nal assembly is anchored securely.