CG10 Burner Manual
Figure 11. Shutter and Band
Table 2. Initial burner settings
Furnace Pressure
0” W.C.
0.25” W.C.
0.50” W.C.
1.00” W.C.
Firing Rate MBH
Burner Model
Running Manifold 
Gas Press. in WC
Low Fire Start Gas 
Press. in WC
Shutter Setting
Band Setting
Running Manifold 
Gas Press. in WC
Low Fire Start Gas 
Press. in WC
Shutter Setting
Band Setting
Running Manifold 
Gas Press. in WC
Low Fire Start Gas 
Press. in WC
Shutter Setting
Band Setting
Running Manifold 
Gas Press. in WC
Low Fire Start Gas 
Press. in WC
Shutter Setting
Band Setting
Stepped Spud Head Confi guration
300
CG10.1S
1.0
0.5
3
0
1.3
0.6
3
0
1.5
0.8
4
0
2.0
1.0
6
0
350
CG10.1S
1.4
0.7
4
0
1.6
0.8
4
0
1.9
0.9
5
0
2.4
1.2
7
0
400
CG10.2S
1.1
0.5
4
0
1.3
0.7
4
0
1.6
0.8
5
0
2.1
1.0
6
0
450
CG10.2S
1.4
0.7
5
0
1.7
0.8
6
0
1.9
1.0
7
0
2.4
1.2
9
0
500
CG10.3S
1.2
0.6
6
0
1.5
0.7
7
0
1.7
0.9
8
0
2.2
1.1
10
1
550
CG10.3S
1.3
0.7
8
0
1.6
0.8
9
0
1.8
0.9
10
0
-
-
-
-
600
CG10.4S
2.5
1.3
5
0
2.8
1.4
6
0
3.0
1.5
7
0
3.5
1.8
9
0
700
CG10.4S
3.4
1.7
7
0
3.6
1.8
9
0
3.9
1.9
10
0
4.4
2.2
10
3
800
CG10.5S
3.1
1.6
8
0
3.4
1.7
9
0
3.6
1.8
10
1
4.1
2.1
10
3
900
CG10.5S
4.0
2.0
10
1
4.2
2.1
10
2
4.5
2.2
10
4
5.0
2.5
10
6
1000
CG10.6S
3.2
1.6
10
0
3.4
1.7
10
2
3.7
1.8
10
3
4.2
2.1
10
6
1100
CG10.6S
3.9
1.9
10
2
4.1
2.1
10
4
4.4
2.2
10
5
4.9
2.4
10
10
1200
CG10.6S
4.6
2.3
10
6
4.9
2.4
10
8
5.1
2.6
10
10
-
-
-
-
Spinner Head Confi guration
300
CG10.1
1.5
0.8
3
0
1.8
0.9
3
0
2.0
1.0
4
0
2.5
1.3
5
0
350
CG10.1
2.0
1.0
5
0
2.3
1.1
6
0
2.5
1.3
8
0
3.0
1.5
10
1
400
CG10.2
1.6
0.8
4
0
1.8
0.9
4
0
2.1
1.0
5
0
2.6
1.3
6
0
450
CG10.2
2.0
1.0
4
0
2.2
1.1
4
0
2.5
1.2
5
0
3.0
1.5
8
0
500
CG10.3
1.5
0.8
5
0
1.8
0.9
5
0
2.0
1.0
6
0
2.5
1.3
8
0
550
CG10.3
1.9
0.9
7
0
2.1
1.1
8
0
2.4
1.2
9
0
2.9
1.4
10
1
Notice: The settings in this chart are for reference only. The actual conditions at the installation may require further 
adjustment by the fully qualifi ed and experienced start-up technician.
Notice: The light-off rate must not be set below the low fi re recommendation.  Lower rates will lengthen the time it takes for 
gas to get to the burner head and may cause ignition failures.
ADJUSTMENT SCALE
(FOR SHUTTER AND BAND)
BAND INDICATOR MARK
SHUTTER INDICATOR
SHUTTER
(for low rate adjustments)
adjust this with band fully 
CLOSED
AIR BAND
(for high rate adjustments)
adjust this with shutter fully 
OPEN
= Tighten locking screws securely after adjustments have been made
The shutter and band both 
control the amount of fl ow area 
available for air inlet to the burner.  The greater their 
combined fl ow area, the higher the fi ring rate.  The 
primary differences between the two are their ease of 
adjustment and their total airfl ow area.  The shutter 
turns more easily and has a smaller net fl ow area.  As a 
result we have found the shutter to be better suited for 
low rate adjustments, and the band better suited for high 
rate adjustments.  We recommend that at low rates the 
band be left completely closed until the shutter has been 
fully opened, and that for higher rates the shutter is left 
completely open as the band is opened.
Section: Start the Burner