Instruction Manual – Model CF2300A Oil Burner
5
Form 6104 BCF-23-R0399
Table 2 – Air tube capacity vs. firebox pressure
Figure 2 – Air tube mounting dimensions
2304
E
D
G
T
1
F
Insertion depth
Air tube to inside of chamber
– 0.25" ± 0.125"
Air tube length
Tube diameter
Figure 1 – Min. combustion chamber dimensions
Install the burner with a 2° pitch as shown.
2305
A
L
❏  
Verify firing rate
• Refer to appliance manufacturer’s instructions (if avail-
able) for firing rate and nozzle selection. Otherwise, the
maximum recommended firing rate for the burner depends
on the length of the firing chamber and the distance from
the burner center to the chamber floor. Verify that the cham-
ber dimensions are at least as large as the minimum values
given in 
Figure 1
. If the appliance dimensions are smaller
than recommended, reduce the firing rate accordingly.
❏  
Verify air tube
• The information in this section may be disregarded if the
air tube is supplied by the appliance manufacturer.
• Two tube arrangements are available –
Tube 
KG
 —   7.0 to 19.9 GPH per 
Table 2
Tube 
KS
 — 10.0 to 19.9 GPH per 
Table 2
• Maximum firing capacity depends on the firebox pressure.
Use 
Table 2
 to verify the correct air tube type for the firing
rate required. Use Tube 
KS
 only when Tube 
KG
 cannot
provide the firing rate required.
• See 
Figure 2
 to verify the correct air tube length and air
tube combination code.
Firing rate
 
Minimum dimensions
(refractory-lined)
(wet-base boilers)
A
L
A
L
  5 to 10 gph
  8.0"
35.0"
8.0"
40.0"
10 to 15 gph
  9.0"
40.0"
9.0"
50.0"
15 to  20 gph
  11.0"
55.0"
11.0"
60.0"
A.T.C. Codes
(A.T.C. = Air Tube Combination)
Tube KG
Tube KS
(Dim
 T
)
(Dim
 D
)
(Dim
 F
)
(Dim
 T
)
(Dim
 D
)
(Dim
 F
)
All —
6¹⁄₂
2¹⁵⁄₁₆
All —
8¹⁄₈
3¹¹⁄₁₆
6¾”
CF   66 KG
6¾”
CF   66 KS
8¾”
CF   86 KS
10¼”
CF 102 KG
11”
CF 110 KS
13¾”
CF 136 KG
14½”
CF 144 KS
17¾”
CF 176 KG
18½”
CF 184 KS
Firebox 
pressure
(In. w.c.)
Tube KG
Tube KS
No reserve 
air
10% 
turndown
No reserve 
air
10%
turndown
0.0
19.9 GPH
19.9 GPH
19.9 GPH
19.9 GPH
0.2
19.2 GPH
19.1 GPH
19.7 GPH
19.6 GPH
0.4
18.5 GPH
18.3 GPH
19.5 GPH
19.3 GPH
0.6
17.9 GPH
17.6 GPH
19.4 GPH
19.1 GPH
0.8
17.2 GPH
16.8 GPH
19.2 GPH
18.8 GPH
1.0
16.5 GPH
16.0 GPH
19.0 GPH
18.5 GPH
Note:  10% turndown indicates sufficient reserve air to reduce the CO
2
 in the 
flue to 90% of its value.
Note: The above ratings may vary 5% due to variations in actual job conditions.