VII. Electrical
A.
  Install Boiler Wiring
1.  Knockdown boilers only.  Locate wiring harnesses 
in Combination Boiler Parts and Control Carton.  
Refer to Table 10 and connect wiring as shown on 
the appropriate wiring diagram.
2.  Connect supply wiring and electrically ground boiler 
in accordance with requirements of authority having 
jurisdiction, or in absence of such requirements the 
National Electrical Code, ANSI/NFPA 70 and/or 
CSA C22.1 Electrical Code.
B.
  Wire Vent Damper (if used; optional on 806H - 
810HE).  See Figure 24.  Vent damper harness for 805 
plugs directly into Hydrostat 3200.
 
NOTE:  Once vent damper is connected to Hydrostat 
3200, control will not operate without it plugged in.
1.  Attach Vent Damper Harness to mounting hole in 
Jacket Left Side Panel.  Install Cable Clamp around 
flexible conduit and attach to Jacket Top Panel.
2.  Remove factory installed Jumper Plug from Vent 
Damper Receptacle on Vestibule Wiring Harness 
and discard.
3.  Plug Vent Damper Harness Plug into Vent Damper 
Receptacle.  See Figure 24.
C.
  Install thermostat.  Locate on inside wall 
approximately 4 feet above floor. Do not install on 
outside wall, near fireplace, or where influenced 
by drafts or restricted air flow, hot or cold pipes, 
lighting fixtures, television, or sunlight. Allow free air 
movement by avoiding placement of furniture near 
thermostat.
 
Set heat anticipator to match control system 
requirements.  Refer to Table 9.
D.
  Wire thermostat.  Provide Class II circuit between 
thermostat and boiler. Refer to appropriate wiring 
diagram for control system being used.
Figure 26:  Vent Damper Schematic Wiring Diagram (806H - 810HE)
Failure to properly wire electrical connections to the boiler may result in serious physical harm.
Electrical power may be from more than one source.  Make sure all power is off before attempting any 
electrical work.
Each boiler must be protected with a properly sized fused disconnect.
Never jump out or make inoperative any safety or operating controls.
The wiring diagrams contained in this manual are for reference purposes only.  Each boiler is shipped with 
a wiring diagram attached to the front door.  Refer to this diagram and the wiring diagram of any controls 
used with the boiler.  Read, understand and follow all wiring instructions supplied with the controls.
Positively assure all electrical connections are unpowered before attempting installation or service of 
electrical components or connections of the boiler or building.  Lock out all electrical boxes with padlock 
once power is turned off.