IX. Service
A.
  General.  Inspection and service must be conducted 
annually. Turn off electrical power and gas supply while 
conducting service or maintenance. Follow instructions 
TO TURN OFF GAS TO APPLIANCE. See Lighting/
Operating Instructions on inside of Front Removable 
Door.
Label all wires prior to disconnection when 
servicing controls.  Wiring errors can cause 
improper and dangerous operation.  Verify proper 
operation after servicing.
B.
  Maintenance of Low Water Cut-off (if used). Follow 
instruction manual provided with low water cut off.  
If model 805, see Installation and Operating manual 
for Hydrostat 3200, packed in envelope taped to top 
of boiler for packaged boilers and in parts and control 
carton for KD boilers for maintenance.
C.
  Vent System. Check for: 
1.  obstructions 
2.  accumulations of soot 
3.  deterioration of vent pipe or vent accessories due to 
condensation or other reasons
4.  proper support—no sags, particularly in horizontal 
runs 
5.  tightness of joints. Remove all accumulations of 
soot with wire brush and vacuum
 
Remove all obstructions. Replace all deteriorated parts 
and support properly. Seal all joints. 
D.
  Remove Main Burners for cleaning, changing orifice 
plugs, or repairs. 
1.  Shut down gas boiler in accordance with Lighting/
Operating Instructions on inside of Front Removable 
Door. Close Manual Shut-off Valve.
2.  Remove Front Removable Door. Raise Lower Front 
Tie Bar.
3.  Disconnect ignition system. 
4.  Remove burner access panel(s). 
5.  Mark location of Main Burner with Pilot Bracket on 
manifold. 
6.  Remove hitch pin clips from Main Burner Orifices. 
7.  Hold Main Burner on throat. Lift slightly to raise 
rear of burner. Push to rear of boiler until burner 
clears Main Burner Orifice. Lift burners out.
8.  Check burners to be sure they do not contain foreign 
matter or restrictions. Clean burners with a soft 
bristle brush, blow any dirt out with compressed air 
or use a vacuum cleaner. See Figure 48. 
E.
  Clean Boiler Flueways.  See Figure 48.
1.  Shut down gas boiler in accordance with Lighting/
Operating Instructions on inside of Front Removable 
Door.  Close Manual Shut-off Valve.
2.  Disconnect vent system. Remove Draft Hood.
3.  Remove Jacket Top Panel.
4.  Remove Canopy from top of boiler. 
5.  Remove flue baffles. Refer to Figure 48 for 
instructions on how to remove baffles from 
flueways.  Remove any accumulated scale or soot.
6.  Thoroughly clean flueways with flue brush, 
removing all scale and soot. See Figure 48.
7.  Clean boiler heating surface accessible from 
combustion chamber with straight handle wire 
brush.
8.  Reinsert baffles into flueways by reversing steps 
given in Figure 48.  Tabs at top of each baffle should 
rest on top of flue pins.
Service on this boiler should be undertaken only by trained and skilled personnel from a qualified service 
agency.  Inspections should be performed at intervals specified in this manual.  Maintain manual in a 
legible condition.
Keep  boiler  area  clear  and  free  of  combustible  materials,  gasoline  and  other  flammable  vapors  and 
liquids.
Do not place any obstructions in boiler room that will hinder flow of combustion and ventilation air.
The service instructions contained in this manual are in addition to the instructions provided by the 
manufacturer of the boiler components.  Follow component manufacturer’s instructions.  Component 
manufacturer’s instructions were provided with the boiler.  Contact component manufacturer for replace-
ment if instructions are missing.  Do not install, start up, operate, maintain or service this boiler without 
reading and understanding all of the component instructions.  Do not allow the boiler to operate with 
altered, disconnected or jumpered components.  Only use replacement components identical to those 
originally supplied by Burnham Commercial.