Burnham Series 8H/8HE Boiler Instruccion De Instalación

Descargar
Página de 84
8
I.  Pre-Installation
Carefully read all instructions before installing 
boiler.  Failure to follow all instructions in proper 
order can cause personal injury or death.
A.
  Inspect shipment carefully for any signs of damage. 
All equipment is carefully manufactured, inspected 
and packed. Our responsibility ceases upon delivery 
of boiler to carrier in good condition. Any claim 
for damage or shortage in shipment must be filed 
immediately against carrier by consignee. No claims 
for variances or shortages will be allowed by Boiler 
Manufacturer, unless presented within sixty (60) days 
after receipt of equipment.
B.
  Installation must conform to the requirements of 
the authority having jurisdiction. In the absence of 
such requirements, installation must conform to the 
National Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or 
CAN/CSA B149.1 Installation Codes.  Where required 
by the authority having jurisdiction, the installation 
must conform to the Standard for Controls and Safety 
Devices for Automatically Fired Boilers, ANSI/ASME 
No CSD-1.
C.
  Provide clearance between combustible material and 
boiler jacket (following clearances are minimums):
1.  USA, 805H-807HE:  listed for Alcove installation
a.  Front:  18”
b.  Top:  36”
c.  Draft hood, rear, sides and flue connector:  6”
Appliance  is  design  certified  for  installation  on 
noncombustible  flooring  only.    For  installation 
on  combustible  flooring  only  when  installed  on 
special base listed in Table 2.  Boiler must not be 
installed on carpeting.  When boiler is installed on 
concrete which is over a material that is subject 
to melting (PVC, PEX radiant tubing, etc.), the 
special base must be used.  A concrete pad is not 
sufficient to protect combustible flooring.
2.  USA, 808HE-810HE:  for installation in room 
which is large in comparison with size of boiler.
a.  Front:  18”
b.  Top:  51½”
c.  Draft hood, rear, sides, and flue connector:  6”
3.  Canada, 805H-810HE:
a.  Top and front:  18” (45.7 cm)
b.  Flue, rear and sides:  6” (15.2 cm)
D.
  Provide clearance for servicing and proper operation 
(following clearances are recommended and may be 
reduced to minimum clearances shown above):
1.  Single boiler, 805H-807HE, Front/Top: 24” (61.0 
cm)
2.  Single boiler, 808HE-810HE, Front/Top: 48”
      (122.0 cm)
3.  Multiple/modular boiler, USA /Canada, Sides:  1” 
(2.5 cm)
E.
  Install boiler on level floor as close to chimney as 
possible. For basement installation provide a solid base 
such as concrete or masonry construction if floor is not 
level or if water may be encountered on floor around 
boiler.
F.
  Protect gas ignition system components from 
water (dripping, spraying, rain, etc.) during boiler 
operation and service (circulator replacement, control 
replacement, etc.).
G.
  Provide combustion and ventilation air in accordance 
with applicable provisions of local building codes, 
or the National Fuel Gas Code, NFPA 54/ANSI 
Z223.1, Air for Combustion and Ventilation; or CAN/
CSA B149.1, Venting Systems and Air Supply for 
Appliances.
Adequate combustion and ventilation air must be 
provided to assure proper combustion.
 
The following guideline is based on the National Fuel 
Gas Code, NFPA 54/ANSI Z223.1.
1.  Determine volume of space (boiler room). Rooms 
communicating directly with space (through 
permanent openings not furnished with doors) are 
considered part of space.
  Volume [ft
3
] = Length [ft] x Width [ft] x Height [ft]
2.  Determine Total Input of all appliances in space.
  Round result to nearest 1,000 Btu per hour (Btuh).
3.  Determine type of space. Divide Volume by Total 
Input.
a.  If result is greater than or equal to 50 ft
3
 per 
1,000 Btuh, space is considered an unconfined 
space.
Boiler Model
Special Base Part Number
805H
61816055
806H
61816065
807HE
61816075
808HE
61816085
809HE
61816095
810HE
61816105
Table 2:  Special Base Required for Installation on 
Combustible Flooring