Burnham FREEDOM 101008-01R1-2/07 Manual De Usuario
61
TABLE 14.3: SOFT LOCKOUT CODES DISPLAYED
CODE
CONDITION
POSSIBLE CAUSES
b 08
Pressure switch circuit open
• Blockage in intake or vent system.
• Vent and/or intake system not constructed in accordance with Part VI.
• Blocked or leaking pressure switch tubing
• Heat exchanger or burner blockage
• Terminals exposed to high winds
• Blockage in condensate trap above vent.
• Vent and/or intake system not constructed in accordance with Part VI.
• Blocked or leaking pressure switch tubing
• Heat exchanger or burner blockage
• Terminals exposed to high winds
• Blockage in condensate trap above vent.
b 18
MCBA supply sensor detected temperatures in excess
of 200°F
of 200°F
• Heating load at time of error was far below the minimum fi ring rate of the
boiler
• Defective primary pump or no fl ow in primary loop (Piping Method 1)
• Control system miswired so that boiler operation is permitted when no
• Control system miswired so that boiler operation is permitted when no
zones are calling
b 19
MCBA return sensor detected temperatures in excess
of 200°F
of 200°F
• See possible causes for “b18”
• Flow through boiler reversed
• Sensor wiring reversed
• Flow through boiler reversed
• Sensor wiring reversed
b 24
MCBA is reading a return sensor temperature higher
than the supply sensor temperature. Condition must be
present for at least 75s for this error code to appear.
than the supply sensor temperature. Condition must be
present for at least 75s for this error code to appear.
• Flow through boiler reversed. Verify correct piping and pump orientation.
• No boiler water fl ow. Verify that system is purged of air and that
• No boiler water fl ow. Verify that system is purged of air and that
appropriate valves are open.
• Sensor wiring reversed.
• Supply or return sensor defective.
• Supply or return sensor defective.
b 25
Supply water temperature has risen too quickly
• See possible causes for “b18”
• Inadequate boiler water fl ow. Verify that pump is operating and that pump
• Inadequate boiler water fl ow. Verify that pump is operating and that pump
and piping are sized per Part VIII of this manual
b 26
Boiler safety limit, or external limit wired across
terminals 3&4, is open.
terminals 3&4, is open.
• See possible causes for “b18”
• Defective supply sensor.
• Defective supply sensor.
b 30
Temperature rise between supply and return is too high.
• Inadequate boiler water fl ow. Verify that pump is operating and that pump
and piping are sized per Part VIII of this manual
b 61
Pressure switch circuit closed with fan off
• Blockage in pressure switch hose
• Pressure switch wires shorted together
• Defective pressure switch
• Loose or miswired fan speed harness (if “b61” error code is observed
• Pressure switch wires shorted together
• Defective pressure switch
• Loose or miswired fan speed harness (if “b61” error code is observed
while fan is running)
b 65
Fan is not achieving set point speed
• Loose or incorrect fan speed control connection
• Defective fan
• Defective fan
B. Trouble shooting problems where a soft lockout code is displayed. When a soft lockout occurs, the boiler will shut down
and the display will alternate between the number “9” and the letter “b” followed by a two digit service code. The boiler
will automatically restart once the condition that caused the lockout is corrected.
will automatically restart once the condition that caused the lockout is corrected.