D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 29 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
• 
• 
• 
• 
• 
• 
• 
• 
• 
• 
• 
• 
When you program AC Fail Time, if the second digit 
is: 
7 (such as 7, 17, 27, 37, and so on): The AC 
Fail Time interval is in minutes. An AC Fail Event 
is only sent after 6 hours if the AC Fail condition 
is still present. 
1, 3, or 5 (such as 3, 5, 11, 13, 15, 21, and so 
on):
 The AC Fail Time interval is in minutes and 
an AC Fail Event is sent after the loss of AC for 
this amount of time. 
No additional AC Fail Events are sent after 6 
hours or 12 hours.  
8 (such as 8, 18, 28, 38, and so on): The AC 
Fail Time interval is in seconds. An AC Fail Event 
is only sent after 6 hours if the AC Fail condition 
is still present. 
2, 4, or 6 (such as 2, 4, 6, 12, 14, 16, 22, 24, 26, 
and so on):
 The AC Fail Time interval is in 
seconds and an AC Fail Event is sent after the 
loss of AC for this amount of time.  
No additional AC Fail Events are sent after 6 
hours or 12 hours. 
9 (such as 9, 19, 29, 39, and so on): The AC 
Fail Time interval is in minutes. An AC Fail Event 
is only sent after 12 hours if the AC Fail condition 
is still present. 
0 (such as 10, 20, 30, and so on): The AC Fail 
Time interval is in seconds. An AC Fail Event is 
sent after 12 hours only if the AC Fail condition is 
still present. 
7 (such as 7, 17, 27, 37, and so on): The AC 
Fail Time interval is in minutes and an AC Fail 
Event is sent after the loss of AC for this amount 
of time. 
An additional AC Fail Event is sent after 6 hours 
if the AC Fail condition is still present. 
 
8 (such as 8, 18, 28, 38, and so on): The AC 
Fail Time interval is in seconds and an AC Fail 
Event is sent after the loss of AC for this amount 
of time. 
An additional AC Fail Event is sent after 6 hours 
if the AC Fail condition is still present. 
9 (such as 9, 19, 29, 39, and so on): The AC 
Fail Time interval is in minutes and an AC Fail 
Event is sent after the loss of AC for this amount 
of time. 
An additional AC Fail Event is sent after 12 hours 
if the AC Fail condition is still present. 
0 (such as 10, 20, 30, and so on): The AC Fail 
Time interval is in seconds and an AC Fail Event 
is sent after the loss of AC for this amount of 
time. 
An additional AC Fail Event is sent after 12 hours 
if the AC Fail condition is still present. 
For the following items to be true, AC Fail/Res Rpt 
must be programmed as No and AC Tag Along must 
also be programmed as No
When you program AC Fail Time, if the second digit 
is: 
1, 3, or 5 (such as 3, 5, 11, 13, 15, 21, and so 
on):
 The AC Fail Time interval is in minutes. No 
AC Fail or AC Restoral Events are sent. 
2, 4, or 6 (such as 2, 4, 6, 12, 14, 16, 22, 24, 26, 
and so on):
 The AC Fail Time interval is in 
seconds. No AC Fail or AC Restoral Events are 
sent. 
To eliminate AC Reporting, AC Tag 
Along
 and AC Fail/Res Rpt must be 
programmed as No and the second digit 
 
of the AC Fail Time must be a 1, 2, 3, 4, 
5, or 6. 
 
AC Fail Display 
Default: 
60 sec 
Selection: 
10 to 300 sec (in 5-sec 
increments) 
 
Program the length of time the AC power must be off 
before the message SERVC AC FAIL shows on the 
keypads. The response to restoral of AC power is 
delayed for the same amount of time. 
 
AC Fail/Res Rpt 
Default: 
No 
Selection: 
Yes or No 
Yes 
Send AC Fail and AC Restoral 
Reports. 
No 
Does not send AC Fail and AC 
Restoral Reports. 
AC Power Supervision Reports are sent to the central 
station and local printer at the time programmed for 
AC Fail Time