D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 51 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
2.10  Keypad (Command Center) 
This programming module contains three programming categories: Cmd Cntr Assignment, Area Text, and 
Custom Function. 
2.10.1  Keypad (Command Center) Assignment 
This programming category assigns a keypad to an area and determines if the keypad is supervised. The 
keypads are connected to the control panel using a two-wire serial data interface (SDI) bus. 
This bus can support up to eight supervised keypads, each with its own unique keypad address (CC) and 
corresponding DIP switch address settings. If the keypads are not supervised, you can install multiple keypads 
with the same DIP switch address setting for up to 32 unsupervised keypads. 
Cmd Center 
Default: 
Selection: 
1 to 8 
DIP Switch Setting 
SDI 
CC# 
Address 
Number 
1 2 3 4 5 6 
ON ON ON ON  --  ON 
OFF 
ON ON ON -- ON 
ON 
OFF 
ON ON -- ON 
OFF 
OFF 
ON ON -- ON 
5 5 
ON  ON OFF ON  --  ON 
6 6 
OFF ON OFF ON  --  ON 
ON 
OFF 
OFF 
ON -- ON 
OFF 
OFF 
OFF 
ON -- ON 
Enter the keypad (CC) number for the SDI address you are programming. This number corresponds to the DIP 
switch address settings shown. 
 
 
CC# Supervised 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
Ye
Only one keypad can be installed for this CC 
SDI address. 
No 
More than one keypad can be installed using 
this CC SDI address with the same address 
DIP switch setting. 
Supervise this SDI address and generate Trouble SDI 
Reports and local trouble annunciation if a problem 
occurs with this keypad or the SDI bus. 
 
 
To meet UL 864 requirements, set CC# 
Supervised
 to Yes for the fire 
annunciation keypad. 
 
Keypads that share the same address 
setting display the same text and emit the 
same tones, regardless of which keypad’s 
 
keys are pressed. 
Trouble SDI # Reports are always 
reported as Area 1, Account 1 Events 
regardless of the area the SDI device is 
assigned. 
 
When this prompt is Yes, you cannot 
have duplicate DIP switch settings. 
 
 
When a D1260 Alpha V Keypad is 
assigned to a keypad address, you must 
program CC# Enhanced Command 
 
Center as Yes