Beckett AQUASMART 7600 Manual De Usuario

Descargar
Página de 36
25
AquaSmart Boiler Control Manual
To ensure smooth appliance operation, the AquaSmart 
requires a separation between the High and Low limits 
no less than the greater differential plus 5°F.  For 
example: If the HIGH LIMIT is set to 180°F, the HIGH 
DIFF to 20°F, and the LOW DIFF to 10°F, the control will 
not allow a LOW LIMIT above 155°F (180°F - 20°F [the 
greater of the two differentials] - 5°F = 155°F). 
A. Temperature High Limit
In any mode or screen other than an OPTION sub-
menu, press the 
“HIGH LIMIT”
 key.
The following screen will be displayed:


  
The temperature displayed is the current setting.  
Use the 
 and 
▼ 
keys to select the desired setting.
Tap the button to increase or decrease the 
temperature by 1°, or hold it to increase or 
decrease the temperature by 5° at a time.  The 
control will not allow you to select out-of-range 
values.
Press the 
“ENTER (RESET)”
 key. 
The control will ask you to confi rm the setting with 
1.
2.
3.
4.
the following screen: 


Press 
“ENTER (RESET)”
 if the value is correct, or 
“CANCEL (BACK)”
 if it is not.
B. Temperature Low Limit
In any mode or screen other than an OPTION sub-
menu, press the 
“LOW LIMIT”
 key.
The following screen will be displayed:


  
The temperature displayed is the current setting.  
Use the 
“▲”
 and 
“▼”
 keys to select the desired 
setting. Tap the button to increase or decrease the 
temperature by 1°, or hold it to increase or 
decrease the temperature by 5° at a time.  The 
control will not allow you to select out-of-range 
values.  For cold-start operation, turn the low limit 
off by pressing the down arrow key repeatedly until 
OFF is displayed. 
IMPORTANT:  To prevent fl ue gas condensation 
and reduce fatigue caused by thermal cycling on 
conventional (non-condensing) boilers, the LOW 
LIMIT set point should be 150° F or above. 
NOTE: Appliance manufacturer’s temperature 
requirements supersede this recommendation. 
Press the 
“ENTER (RESET)”
 key. 
The control will ask you to confi rm the setting with 
the following screen: 


Press 
“ENTER (RESET)”
 if the value is correct, or 
“CANCEL (BACK)”
 if it is not.
C. Temperature High Limit Differential
In any mode or screen other than an OPTION sub-
menu, press the 
“HIGH DIFF”
 key.
The following screen will be displayed:


  
The temperature displayed is the current setting.  
Use the 
“▲”
 and 
“▼” 
keys to select the desired 
setting. Tap the button to increase or decrease the 
temperature by 1°, or hold it to increase or 
decrease the temperature by 5° at a time.  The 
control will not allow you to select out-of-range 
values.
1.
2.
3.
4.
1.
2.
Programming Basic Functions
Figure 18 - AquaSmart Keypad
Electrical Shock Hazard.
Can cause severe injury, death, or equipment damage.
Live line voltage wires and connections will be exposed 
while programming the AquaSmart.  Take care to touch only 
the AquaSmart keypad while programming the control.
Fire, Explosion, and Burn 
Hazards.
Can cause severe injury, death, or equipment damage.
Do not set the operating limits of the control outside of 
those listed by the appliance manufacturer.