White Rodgers 1C26 Manual De Usuario

Descargar
Página de 4
SET HEAT ANTICIPATOR
Set anticipator to match the setting of your old thermostat you
noted in Step 3, or, the anticipator should be set to match the
current rating stamped on your main heating control. The heat
anticipator is adjustable from 0.15 to 1.2 amps. Adjust the antici-
pator by rotating the contact arm (see fig. 5). The anticipator
setting is indicated by the numbers on the base that the pointer
points to. If you are unsure where to set the anticipator contact the
heater manufacturer for a recommended setting.
Move the pointer 
counterclockwise to lengthen
 heating system
cycles; move 
clockwise to shorten
 heating cycles. Adjustments
should not be greater than 1/2 marking at a time.
Snap on Cover: Carefully align the cover with the base and snap
the cover onto the base.
NEW THERMOSTAT OPERATION
1C20 Heat Only –
 After power is turned on, slide temperature
lever to desired setting. To turn heat off, slide lever all the way to
the left until it clicks.
1C26 – 
This thermostat is easy to operate. Fig. 6 shows how the
heating/cooling system and fan operate when the switches are in
various positions. After power is turned on, use the system switch
to select either heating or cooling, or to turn the heating/cooling
system off. Use the fan switch to control fan operation. When the
fan switch is in the 
AUTO
 position, the fan will cycle with the
heating or cooling system (the fan will not run if the system switch
is in the 
OFF
 position and the fan switch is in the 
AUTO 
position).
When the fan switch is in the 
ON
 position, the fan will run
continuously, regardless of system switch position (even if the
system switch is set to 
OFF
, the fan will run if the fan switch is in
the 
ON
 position).
ELECTRICAL DATA
Switch Rating
........................ 24 VAC (30 VAC max.)
Heating .................................... 0.15 to 1.2 Amps
Cooling .................................... 0 to 1.5 Amps
Switch Action
........................ Snap Action
Anticipator Rating:
Heating .................................... Adjustable from 0.15 to 1.2 Amps
Cooling .................................... Fixed
SPECIFICATIONS
THERMAL DATA:
Temperature Range ..............
50°F to 90°F (10°C to 32°C)
Operating Humidity Range ...
0 – 90% noncondensing
24VAC 
50/60 Hz 
.35 Amps
Typical Zone Valve
24VAC 
50/60 Hz 
.23 Amps
Typical Gas Valve
24VAC
50/60 Hz 
.43 Amps
Typical Oil Primary
www.white-rodgers.com
5
6
7
Figure 5. Anticipator adjustment
Rotate contact arm 
to adjust heat anticipator
Arrow points to the 
current rating of 
the primary coontrol
NOTE
For Milivolt Application:
Rotate contact arm
to rest on this rivet.
FAN
AUTO
ON
SYSTEM
COOL OFF HEAT
Shows switch position
OPERATION
No heating; no cooling; no fan
No heating; no cooling; fan runs continuously
Cooling system cycles from thermostat; fan runs
continuously
Cooling system and fan cycle from thermostat
Heating system cycles from thermostat; fan cycles
from fan control on furnace
Heating system cycles from thermostat; fan runs
continuously
Figure 6. Subbase switching and thermostat/system 
operation (1C26 only)