5
INSTALLER/CONFIGURATION MENU
Entering and Navigating the Advanced Installer Configuration Menu
On the Home Screen Display, touch the 
Menu key to display additional key choices. Touch and hold the Installer Config key 
for approximately 3 seconds to enter the Thermostat Options Configuration Menu. Touch and hold the 
Installer Config key 
again for approximately 3 seconds to enter the Advanced Installer Configuration Menu.
Ref.
#
Description of 
Features in order when 
using 
 
to  choose;
(Use 
 
to step back)
Press 
 or 
 Key 
to Select Options
Displayed in 
Message Area
Displayed in 
Clock Digits 
(Default)
Options
1
Outdoor / Condenser
Configuration
AC1
AC0, AC1, AC2, HP1, HP2
CONDENSER 
CONFIG
2
Indoor Heat
Configuration
GA2
FAN, GA1, GA2, EL1, EL2
INDOOR HEAT
CONFIG
3
B or O terminal
(HP1, HP2 only)
O
O, b
REVERSING VALVE
4
Heat Cycle Rate
FA
SL, FA
HEAT CYCLE RATE
5
Cool Cycle Rate
FA
SL, FA
COOL CYCLE RATE
6
Auxiliary Cycle Rate 
(HP1, HP2 only)
FA
SL, FA
AUXILIARY CYCLE
RATE
7
Energy Management
Recovery
On
OFF, On
ENERGY MANAGEMENT 
RECOVERY
8
Outdoor Remote
Sensor
OFF
OFF, On
OUTDOOR REMOTE SENSOR
9
Auxiliary Off
(HP1, HP2 only)
OFF
OFF, 35-80 (in steps of 1 degree)
 
From
 OFF, value changes to 80
AUXILIARY OFF
10
Dual Fuel Config
(HP1, HP2 only)
40
OFF
0 to 50 (in steps of 1 degree)
From
 OFF, value changes to 40
DUAL FUEL CONFIG
11
Dehumidification
OFF
OFF
, 40-80 (in 1% steps) - displayed 
in the last digits of the Message Area.
From
 OFF, value changes to 60
DEHUM XX% (where XX 
is the DEHUM set point)
12
Independent
Dehumidification
OFF
OFF, On
INDEPENDENT DEHUMID
13
Humidification
OFF 
OFF, 20-60 (in 1% steps) - displayed 
in the last digits of the Message Area. 
From 
OFF,  value  changes  to  40                                                            
HUMID XX% (where XX 
is the HUM set point)
14
Independent
Humidification
OFF
OFF, On
INDEPENDENT
HUMID
15
Compressor Lockout
OFF
OFF, On
COMPRESSOR LOCKOUT