INSTALLER/CONFIGURATION MENU
1)  This control can be confi gured for:
 
MS 2 – Multi-Stage System (no heat pump)
 
HP 1 – Heat Pump with one stage of compressor
 
HP 2 – Heat Pump with two stage compressor or two 
            compressor system, Gas or Electric backup
 
SS 1 – Single Stage System
2)  GAS or Electric (ELE) fan operation. If the heating system 
requires the thermostat to energize the fan, select ELE. 
Select GAS if the heating system energizes the fan on a  
call for heat.
3)  Energy Management Recovery: (this step is skipped if 
confi gured to be non-programmable). 
 
Energy Management Recovery (E) On enables the ther- 
mostat to start heating or cooling early to make the building 
temperature reach the program setpoint at the time you  
specify. Heating will start 5 minutes early for every 1° of 
temperature required to reach setpoint.
 
Example: E On is selected and your heating is pro-   
grammed to 65° at night and 70° at 7 AM. If the building 
temperature is 65°, the difference between 65° and 70° is 
5°. Allowing 5 minutes per degree, the thermostat setpoint  
will change to 70° at 6:35 AM. Cooling allows more time 
per degree, because it takes longer to reach set tempera-
ture.
4, 5 & 6) Cycle Rate Selection – The factory default setting for 
Heat and Cool modes, SS1, MS2, is medium cycle (ME). For 
Heat Pump, HP1, HP2, the default setting is medium (ME). 
For Aux the default setting is fast cycle (FA). To change cycle 
rate, press the 
 or 
 button.
 
Cycle rate differentials for different settings are:
7)  Select Compressor Lockout CL OFF or ON – Selecting 
CL ON will cause the thermostat to wait 5 minutes be-
tween cooling cycles. This is intended to help protect the 
compressor from short cycling. Some newer compressors 
already have a time delay built in and do not require this 
feature. Your compressor manufacturer can tell you if the 
lockout feature is already present in their system. When 
the thermostat compressor time delay occurs, it will fl ash 
the setpoint for up to fi ve minutes.
8)   System Mode Confi guration – This thermostat is confi g- 
ured for Heat and Cool (SYSTEM switch with Cool Off  
Heat) default. It can also be confi gured for Heat and Cool  
(Heat, Cool, Off), Heat only with fan (Off Heat), Heat only 
without fan, and Cool only (Cool Off).
9)  Compressor Optimization – CO provides a delay in cir-
culator fan operation after the compressor turns on or off. 
With CO selected ON, when the compressor turns on (for 
a call for heat in heat pump or a call for cool) the fan will 
be delayed for fi ve seconds before turning on to allow the 
air to be heated or cooled. After the compressor turns off 
for call for cool, the fan will continue to run for 20 seconds 
to circulate all of the cooled air. If CO is set to OFF, there 
will be no delay in fan operation.
10) Select Backlight Display – The display backlight improves 
display contrast in low lighting conditions. When the "C" 
terminal is powered, selecting backlight dL ON will keep the 
light on continuously. Select backlight OFF will turn the light 
on momentarily after any button is pressed. When the "C" 
terminal is not powered, the light will be on momen-  tarily  
after any button is pressed no matter whether the backlight 
is selected ON or OFF.
11) Select Temperature Display Adjustment 4 LO to 4 HI – 
Allows you to adjust the room temperature display up to 4°  
higher or lower. Your thermostat was accurately calibrated  
at the factory, but you have the option to change the dis- 
play temperature to match your previous thermostat. The 
current or adjusted room temperature will be displayed.
12) Select F° or C° Readout – Changes the display readout 
to Celsius or Fahrenheit as required.
13) Program Options: Selects confi guration for 7 day (7) or 
non-programming (0) mode. The default setting is 0, indi-
cating non-programming. The programs per week can be 
changed by pressing the 
 or 
 buttons. A selection 
of 0 days for non-programmable will eliminate the need for 
EMR, and that step in the menu will be skipped.
14) Program Steps per day – This control can be confi gured 
for 4 or 2 program steps per day. Default is "PS" and can 
be toggled between 4 PS and 2 PS.
15 & 16) Select Fast Second Stage ON or OFF – Heat 
pump or Multi-stage only, in the run mode, with the fast 
Heat  feature enabled (FA Heat On), if the Heat setpoint 
temperature is manually raised by 3°F (2°C) or more 
above the actual temperature using 
 the second stage 
will energize immediately. With FA OFF, second stage will 
not energize until the setpoint temperature is 1°F or more  
above actual temperature for more than ten minutes. The  
Fast Cool feature (FA Cool) provides the same controls  
when the setpoint temperature is lowered.
17) Select Daylight Saving Time Calculation – This feature 
will allow the thermostat to calculate the DST automati-
cally and apply it to the Real Time Clock display. Default 
On. Use 
 or 
 touch keys to select the feature OFF.
18) Limited Heat Range – This feature provides a maximum 
setpoint temperature for heat. The default setting is 99°F. It 
can be changed between 62°F and 98°F by pressing the 
 or 
 button.
19) Limited Cool Range – This feature provide a minimum 
setpoint temperature for cool. The default setting is 45°F. It 
can be changed between 46°F and 82°F by pressing the 
 or 
 button. 
20) Select Dual Fuel (dF) – Selects dual fuel setting 0 to 9 
(0 is default OFF,  for Elect AUX) if your system has a fos-
sil fuel (gas or oil) Auxiliary heat. HP1 or HP2 only.
 
Select Compressor Delay (Cd) – After the auxiliary heat 
is turned on, the compressor(s) shut down is delayed for 
the time selected (in seconds). This delay is factory set 
to 60, but can be set in the range of 0 to 99 using 
 or 
 buttons. Available only if dF 1 to 9 is selected above.
21) Select Reversing Valve Output – The O/B option is 
factory set at "O" position. This will accommodate the 
majority of heat pump applications, which require the 
changeover relay to be energized in COOL. If the thermo-
stat you are replacing or the heat pump being installed 
with this thermostat requires a "B" terminal, to energize 
the changeover relay in HEAT, the O/B option should be 
set at "B" position.
 MODE 
 
Fast  Medium 
Slow
 
  FA 
ME 
SL
 
Heat (SS1, MS2) 
0.4°F 
0.6°F 
1.7°F
 
Cool (SS1, MS2) 
0.9°F 
1.2°F 
1.7°F
 
Heat Pump (HP1, HP2) 
0.9°F 
1.2°F 
1.7°F
 
AUX (HP1, HP2) 
0.6°F 
1.7°F