INSTALLER/CONFIGURATION MENU
To enter the menu: Press the
 Menu touch key . Press and hold for 5 seconds the Installer Config touch key . This displays 
screen reference #1 in the table below . Screen Reference numbers appear in top right corner of display . Press 
 to advance 
to the next menu item or 
 to return to a previous menu item . Press   or   to change a menu item option . Shaded items are 
not available if selected for Non-Programmable .
Installer Note: To default the programming, clock and Configuration Menu to the Factory Default Settings, press the  ,   
and SYSTEM keys simultaneously. The thermostat display will go blank for a few seconds, and then all segments will display 
momentarily. 
For heat pump systems, Configuration Menu items 1 and 3 must be set to match the heat pump system.
CONFIGURATION MENU
Screen
Reference
Number
SS1
MS2
HP1
HP2 
Press 
key
Displayed 
Factory 
(Default)
Press 
 or 
 
to select from 
listed options
Comments
1
MS 2
HP 1, HP 2, SS 1
Selects Multi-Stage (MS2, No Heat Pump), Heat Pump 1 
 
 (HP1, 1 compressor), Heat Pump 2 (HP2, 2 compressor  
 
 or 2 speed compressor), or Single Stage .
2
(GAS)
ELE
GAS setting: furnace controls blower .  
 
 
 ELE setting: thermostat controls blower .
3
0b (0)
b
Selects Reversing Valve (This item is only to appear if HP1 or HP2 
is selected above .)
4
Days, 
(7) P
5 or 0
Programs per week . (7 days, 5-1-1 days or non-programmable)
5
Cool-Off-
Heat-Auto
Cool-Off-Heat, Heat Off, 
Heat, Cool-Off, Auto Off
System switch configuration in non heat pump mode .
Cool-Off-Heat-
Em-Auto
Cool-Off-Heat-Em, 
Off-Em-Auto
System switch configuration, heat pump mode .
6
(On) 
E
OFF
Selects Energy Management Recovery . Not available if 4 is 0
7
(FA) Heat, Cr 
SL
Selects Adjustable Anticipation, cycle rate, Heat
8
(FA) Cool, Cr 
SL
Selects Adjustable Anticipation, cycle rate, Cool
9
(FA) Cr/AU, Em
SL
Selects Adjustable Anticipation, cycle rate auxiliary, (This item is  
 only to appear if HP1 or HP2 is selected above) .
10
(OFF) 
CL 
On
Selects Compressor Lockout .
11
(On) 
dL
OFF
Selects Continuous Display backlight .
12
0
(Temperature)
5, LO to 5, HI
Selects Adjustable Ambient Temperature Display [range -5 (LO)         
to +5 (HI)] .
13
°F
°C
Selects °F/°C Display (temperature units in Fahrenheit or Celsius) .
14
(On) 
b
OFF
Selects audible Beeper On/Off .
15
(On) 
dS
OFF
Selects Daylight Saving Time calculation .
16
(On) Heat, 
AS 
OFF
Selects Automatic Schedule for comfort temperature Programming, 
heat mode . Not available if 4 is 0
17
(On) Cool, 
AS 
OFF
Selects Automatic Schedule for comfort temperature Programming, 
cool mode . Not available if 4 is 0
18
(OFF) 
CS  
On
Selects Cool Savings Feature On of Off .
19
CS Cool Savings
(3)
1-2-3-4-5-6
Selects amount of Cool Savings adjustment .
20
(OFF) 
CO
On
Selects Compressor Optimization (not available on earlier models)
21
(OFF) 
CA
On
Selects Comfort Alert Feature On or Off . (not available on earlier 
models)
22
(99) Heat, 
HL 
62-98
TEMPERATURE LIMIT, HEAT (max . heat set point) .
23
(45) Cool, 
LL 
46-82
TEMPERATURE LIMIT, COOL (min . cool set point) .
24
OFF,   
Keypad Lockout
L (total), P (partial), 
Temperature Limit
(limited temperature range)
Selects Keypad Lockout .
25
000
001-999
Selects Keypad Lockout Combination (active only if keypad Lockout
is selected) .
26
MS2
(On) Heat, FS 
OFF
Fast second stage of heat (not available if SS1 is selected above) .
27
MS2
HP2
(On) Cool, FS 
OFF
Fast second stage of cool (not available if SS1 or HP1 
is selected above) .
28
Remote (OFF)
On
Remote temperature sensor, enable/disable .
29
Remote, In 
Outdoor Remote
Remote temperature sensor (Indoor/Outdoor) .
30
(On) LS
OFF
Local temp . Sensor enable/disable (only when Indoor Remote is   
 selected  On) .
31
(OFF) dF
On
Selects Dual Fuel feature On or OFF (this item appears if HP1 or HP2 
is selected above) .
32
(35) dF
-5 - 50
Selects Dual Fuel setpoint (°F), dF selected On with outdoor sensor 
available .
5