INSTALLATION 
batteries should be replaced before leaving. When less than 
two months of battery life remain, the setpoint temperature will 
offset  by  10  degrees  (10  degrees  cooler  in  Heat  mode  /  10 
degrees  warmer  in  Cool  mode).  If  offset  occurs,  the  normal 
setpoint can be manually reset with 
 or 
. Another offset 
will  occur  within  two  days  if  batteries  are  not  replaced.  To 
replace the batteries, set system to OFF.
ENERGY MANAGEMENT RECOVERY 
(EMR)
When  the  Energy  Management  Recovery  (EMR)  feature  is 
activated the thermostat will start the program early to achieve 
the programmed temperature setting by the time specified in 
the program and minimize Auxiliary Heat use. Heat Pump and 
Cooling systems start approximately 15 minutes early for every 
1° of temperature (gas or electric heat starts 5 minutes early 
for  every  1°)  required  to  reach  the  next  temperature  setting. 
This  helps  the  building  warm  up  in  Heating  or  cool  down  in 
Cooling so it reaches the program temperature right on time. 
EMR – Heat Pump Example:
If  the  thermostat  is  programmed  to  an  overnight  heating 
temperature of 66°F, and the next program period, beginning at 
6:00 AM is programmed to 70°F, the thermostat will automatically 
advance the program setting and start the heating system at 
about 5:00 AM. The thermostat will use Heat Pump only during 
the majority of the recovery period. It will use Auxiliary Heat 
only if the thermostat calculates the Heat Pump will not meet 
setpoint by the programmed time. This saves money by using 
the Heat Pump for setback recovery as much as possible and 
using Auxiliary Heat only if the Heat Pump cannot recover by 
the time programmed.
To turn EMR off, use the Configuration Menu on page 5. When 
EMR  is  set  to 
OFF  the  temperature  settings  will  change  at 
exactly your program times. 
WIRING DIAGRAM 
L
R
C
24 VAC
120 VAC
Hot
SYSTEM
MONITOR
SWITCH
Neutral
THERMOSTAT
SYSTEM
G
W2
Figure 2. Typical wiring diagram for single transformer systems
TRANSFORMER
(Class II Current Limited)
Changeover
Relay*
Y
O/B
Compressor
Contactor
Changeover Relay is energized in COOL when O/B switch is in the “O” position
Changeover Relay is energized in HEAT when O/B switch is in the “B” position
The 24 volt neutral connection to terminal C on the thermostat is not required if you
replace the batteries once a year with fresh “AA” alkaline batteries.
Aux/Emergency
Heat Relay
(Stage 2)
Fan
Relay
The 24 volt neutral connection 
to terminal C on thermostat is 
not required if you replace the 
batteries  once  a  year  with 
fresh “AA” alkaline batteries.
NOTE
**
*
**