GAS SUPPLY PIPING
Figure 13 - Gas Piping At Boiler
CAUTION
WHAT TO DO IF YOU SMELL GAS
•  Do not try to light any appliance.
•  Do not touch any electrical switch; do not use 
any phone in your building.
•  Immediately call your gas supplier from a 
neighbor’s phone.  Follow gas supplier’s 
instructions. 
•  If you cannot reach your gas supplier, call the fire 
department.
!
  
General
• Use piping materials and joining methods acceptable 
to authority having jurisdiction.  In absence of such 
requirements National Fuel gas Code, ANSI Z223.1/
NFPA 54.
• Size and install gas piping system to provide sufficient 
gas supply to meet maximum input at not less than 
minimum supply pressure. See Table 6.
Table 6
Natural Gas
Propane
Min. Supply Pressure
5" w/c
11" w/c
Max. Supply Pressure
13.5" w/c
13.5" w/c
Manifold Pressure
3.5" w/c
10.5" w/c
• Support piping with hooks straps, bands, brackets, 
hangers, or building structure components to prevent or 
dampen excessive vibrations and prevent strain on gas 
connection.  Gas valve will not support piping weight.
• Use thread (joint) compound (pipe dope) suitable for 
natural and liquefied petroleum gas.
• Install field sourced manual main shutoff valve, ground 
joint union, and sediment trap upstream of gas valve. 
See Figure 13.
Propane Installation
 WARNING
Fire, explosion, asphyxiation hazard. Verify boiler 
is equipped with propane gas orifices and gas valve 
is configured for propane. Failure to follow these 
instructions may result in serious injury or death.
• Connections by licensed propane dealer only.
• Use two stage regulator provided by propane 
supplier.
• Have propane supplier check piping.
DANGER
Fire Hazard.  Do not use matches, candles, open 
flames, or other methods providing ignition source. 
Failure to comply will result in death or serious 
injury.
!  
Leak Check Gas Piping
Pressure test boiler and gas connection before placing 
boiler in operation. Avoid excessive pressure that could 
damage pressure regulators, valves, or meters.
• Pressure test at 1/2 psig (3.5 kPa) or less.  Isolate 
boiler from gas supply system by closing manual gas 
shutoff valve. 
• Locate leakage using gas detector, noncorrosive 
detection fluid, or other leak detection method 
acceptable to authority having jurisdiction.  Do not 
use matches, candles, open flames, or other methods 
providing ignition source.
• Correct leaks immediately and retest.
!