9.0 
Combustion Air And Flue Vent Exhaust
9.1  The boiler shall allow for single pipe or direct vent installations.  The venting shall be constructed 
of approved materials and installed as per the manufactures written instructions, plan drawings 
and all applicable local code authorities.  Foam core pipe is not an approved vent material and 
Shall Not be used.  
9.2  The combustion air inlet and flue gas exhaust shall directly connect to the boiler at the locations 
labeled.  Boiler shall have the front removable jacket in place during operation.  The jacket can 
be taken off during commissioning and service per the manufactures written service and kit 
instructions
10.0  Condensate Drain
10.1 Boiler shall be equipped with a corrosion resistance polypropylene flue collector. An external drain 
trap shall be installed.  Flue collectors manufactured out of stainless steel or cast aluminum are 
not acceptable.  The drain line external to the boiler shall be constructed of approved materials 
and installed as per the manufactures written instructions, plan drawings and all applicable local 
code authorities.
11.0  Electrical Connections
11.1 Supply voltage 120 volts 60 HZ 12 amp minimum size circuit.  The boiler shall have terminals for 
a system pump and a domestic hot water pump.  The terminals for these pumps shall be rated 
for 120 volts with a 1 amp FLA connections on 100 mbh and smaller, 10 amp FLA on 150 mbh 
and larger.
11.2 The boiler shall have Line voltage and separate Low voltage terminal strips with clearly marked 
connections.
12.0  Quality Assurance
12.1 Warranty - The Boiler shall be supplied with a written manufactures 15 year limited warranty on 
the heat exchanger and 1 year on parts and controls supplied with the boiler.
12.2 Factory Testing – The boiler shall be factory fired tested and a combustion report generated and 
included with the boiler.  
13.0  Boiler Manuals
13.1  The boiler shall be provided with a complete set of instructions and reports as follows:
Installation and Operation Manual (IOM) 
Repair Parts Manual
User’s Manual
Kit Instructions for field installed optional devices