7. Communications parameters
The settings of communication-related parameters can be changed from the operation panel and the
external controller (computer). Note that there are two types of parameters: parameters whose set-
tings take effect immediately after the setting and parameters whose settings do not take effect until
the inverter is turned back on or reset.
external controller (computer). Note that there are two types of parameters: parameters whose set-
tings take effect immediately after the setting and parameters whose settings do not take effect until
the inverter is turned back on or reset.
Com-
munica-
tion
Number.
Title
Function
Adjustment range
Unit
Default
setting
Valid
Reference
0800
Communication
baud rate
baud rate
0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
-
3
After reset.
Section 7.1
0801
Parity
0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)
1: EVEN (Even parity)
2: ODD (Odd parity)
-
1
After reset.
Section 7.1
0802
Inverter number
0-255
1
0
Real time
Section 7.2
0803
Communication
error trip time
error trip time
0: (disabled)
1-100
1-100
1s
0
Real time
Section 7.3
0805
Communication
waiting time
waiting time
0.00-2.00s
0.01s
0.00
Real time
Section 7.4
0806
Setting of master
and slave inverters
for communication
between inverters
(setting of master
and slave)
and slave inverters
for communication
between inverters
(setting of master
and slave)
0: Slave inverter (0 Hz command issued
in case the master inverter fails)
1: Slave inverter (Operation continued in
case the master inverter fails)
2: Slave inverter (Emergency stop trip-
ping in case the master inverter fails)
3: Master inverter (transmission of fre-
quency commands)
4: Master inverter (transmission of output
frequency signals)
-
0
After reset.
Chapter 6
0811
Point 1 setting
0-100
1%
0
Real time
0812
Point 1 frequency
0.0-500.0Hz
0.01Hz
0.0
Real time
0813
Point 2 setting
0-100
1%
100
Real time
0814
Point 2 frequency
0.0-500.0Hz
0.01Hz
60.0
Real time
Section 6.1
0829
Selection of com-
munication proto-
col
munication proto-
col
0: Toshiba inverter protocol
1: Modbus-RTU protocol
1: Modbus-RTU protocol
-
0
After reset.
Chapter 3
0870
Block write data 1
0871
Block write data 2
0: No selection
1: Command information 1
2: Command information 2
3: Frequency command
4: Output data on the terminal board
5: Analog output for communications
1: Command information 1
2: Command information 2
3: Frequency command
4: Output data on the terminal board
5: Analog output for communications
-
0
After reset.
0875
Block read data 1
0876
Block read data 2
0877
Block read data 3
0878
Block read data 4
0879
Block read data 5
0: No selection
1: Status information
2: Output frequency
3: Output current
4: Output voltage
5: Alarm information
6: PID feedback value
7: Input terminal board monitor
8: Output terminal board monitor
9: VIA terminal board monitor
10: VIB terminal board monitor
1: Status information
2: Output frequency
3: Output current
4: Output voltage
5: Alarm information
6: PID feedback value
7: Input terminal board monitor
8: Output terminal board monitor
9: VIA terminal board monitor
10: VIB terminal board monitor
-
0
After reset.
Section
4.1.3
0880
Free notes
0-65535
1
0
Real time
Section 7.5