7.  Communications parameters
The settings of communication-related parameters can be changed from the operation panel and the
external controller (computer). Note that there are two types of parameters: parameters whose set-
tings take effect immediately after the setting and parameters whose settings do not take effect until
the inverter is turned back on or reset.
Com-
munica-
tion
Number.
Title
Function
Adjustment range
Unit
Default
setting
Valid
Reference
0800

Communication
baud rate
0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
-
3
After reset.
Section 7.1
0801

Parity
0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)
-
1
After reset.
Section 7.1
0802

Inverter number
0-255
1
0
Real time
Section 7.2
0803

Communication
error trip time
0: (disabled)
1-100
1s
0
Real time
Section 7.3
0805

Communication
waiting time
0.00-2.00s
0.01s
0.00
Real time
Section 7.4
0806

Setting of master
and slave inverters
for communication
between inverters
(setting of master
and slave)
0: Slave inverter (0 Hz command issued
in case the master inverter fails)
1: Slave inverter (Operation continued in
case the master inverter fails)
2: Slave inverter (Emergency stop trip-
ping in case the master inverter fails)
3: Master inverter (transmission of fre-
quency commands)
4: Master inverter (transmission of output
frequency signals)
-
0
After reset.
Chapter 6
0811

Point 1 setting
0-100
1%
0
Real time
0812

Point 1 frequency
0.0-500.0Hz
0.01Hz
0.0
Real time
0813

Point 2 setting
0-100
1%
100
Real time
0814

Point 2 frequency
0.0-500.0Hz
0.01Hz
60.0
Real time
Section 6.1
0829

Selection of com-
munication proto-
col
0: Toshiba inverter protocol
1: Modbus-RTU protocol
-
0
After reset.
Chapter 3
0870

Block write data 1
0871

Block write data 2
0: No selection
1: Command information 1
2: Command information 2
3: Frequency command
4: Output data on the terminal board
5: Analog output for communications
-
0
After reset.
0875

Block read data 1
0876

Block read data 2
0877

Block read data 3
0878

Block read data 4
0879

Block read data 5
0: No selection
1: Status information
2: Output frequency
3: Output current
4: Output voltage
5: Alarm information
6: PID feedback value
7: Input terminal board monitor
8: Output terminal board monitor
9: VIA terminal board monitor
10: VIB terminal board monitor
-
0
After reset.
Section
4.1.3
0880

Free notes
0-65535
1
0
Real time
Section 7.5