E6581222
54
„
 
Input terminal board status (FD06, FE06)
Input terminal board status (status immediately before the occurrence of a trip):
Communication Number FE06
Input terminal board status (current status):
Communication Number FD06
In case “0: No assignment function” is selected in function selection, inverter operations will not be
affected even when terminals are turned on and off.    Therefore, the terminals can be used as input
terminals for customer’s own use.
The input terminal function selection parameter is used to select a function for each input terminal.
When monitoring the operating status, check what function is assigned to each internal terminal.
Data construction of input terminal board (FE06)
Bit
Terminal name (extended)
Function (parameter title)
0
1
0
  F
Input terminal selection 1 (f111)
OFF
ON
1
  R
Input terminal selection 2 (f112)
OFF
ON
2
  RES
Input terminal selection 3 (f113)
OFF
ON
3
  S1
Input terminal selection 4 (f114)
OFF
ON
4
  S2
Input terminal selection 5 (f115)
OFF
ON
5
  S3
Input terminal selection 6 (f116)
OFF
ON
6
  VIB *1
Input terminal selection 7 (f117)
OFF
ON
7
  VIA *1
Input terminal selection 8 (f118)
OFF
ON
8 ~ 15
-
-
-
-
*
1: It is valid only when it is selected as contact input by .
It is effective only when it is chosen with F109 for input of a contact point.
Ex.: FE06 data when the F and S1 terminals are ON: 0009H
BIT15
BIT0
0
0 0
0
0 0
0
0 0
0
0 0
1
0 0
1
„
 
Output terminal board status (FD07, FE07)
Output terminal board status (status immediately before the occurrence of a trip):
Communication Number FE07
Output terminal board status (current status):
Communication Number FD07
The output terminal function selection parameter is used to select a function for each output terminal.
When monitoring the operating status, check what function is assigned to each output terminal.
Data construction of output terminal board (FD07,FE07)
Bit
Terminal name
Function (parameter title)
0
1
0
RY
  Output terminal selection1(f130)
OFF
ON
1
OUT
  Output terminal selection1(f131)
OFF
ON
2
FL
  Output terminal selection3(f132)
OFF
ON
∼ 15
-
-
-
-
Ex.: FE07 data when both the RY and OUT terminals are ON: 0003H
BIT15
BIT0
0
0 0
0
0 0
0
0 0
0
0 0
0
0 1
1
FE06:
FE07:
0
0
9
3
0
0
0
0