Block Communication Function for LED Display
To display LED data for ASCII display that is synchronized to each digit, set data for each digit and
validate this set data by display selection by communication (Communication Number FA65).
   
Syn-
chronization can also be achieved by batch writing LED data parameters after changing the following
block communication mode parameters and by sending data by block communication.
Writing in the block communication function will be writing in the RAMs only due to the EEPROM life
for write operations.    The LED data will reset to the initial value ““ when the power is turned
off, in failure resetting or when standard
 
shipment settings
 
are set.
■ Parameter Setting
“Block communication mode (Communication Number FA80)”
Setting range: 0, 1 (Initial value 0)
0: Block communication parameters ( - ) is used
1: LED display ASCII data is used (When writing, ASCII display data 1 [Communication Number
FA70 - FA74], when reading, LED data displayed before change)
*To validate LED data set by using LED display block communications, set standard monitor display
selection to “communication LED select ( = ) and display selection by communication to
“ASCII data 1 (Communication Number FA65).
■ Format
The format is the same as that used in the usual block communication mode.    (For the detail infor-
mation, see “4.1.3 Block communication transmission format”)    The block communication parame-
ters ( - ) will become invalid.    Write data will become ASCII display data 1 (Commu-
nication Number :FA70 - FA74) fixed.    LED display data that is actually being output will be read
during reading.    The specification range for write operations is 0 to 5.
■ Example
Assuming:
Communication LED selection ( = ) for standard monitor display selection.
ASCII data 1 (Communication Number:FA65 = 1) for display selection by communication.
LED display ASCII data (Communication Number: FA80 = 1) for the block communication mode.
Current LED display status is display of initial value “”
PC → Inverter: 2F580505003000310032003300035A・・・“0123” display command
Inverter → PC: 2F59050000640041007400410000E7  ・・  “dAtA” displayed before change