Fluid Cooler Cleaning:
Any evaporative-type fluid cooler must be thoroughly cleaned on a
regular basis to minimize the growth of bacteria, including Legionella 
Pneumophila, to avoid the risk of sickness or death. Service personnel
must wear proper personal protective equipment during decontami-
nation. Do NOT attempt any service unless the fan motor is locked
out.
Operators of evaporative cooling equipment, such as closed circuit cool-
ing towers, should follow maintenance programs which will reduce to an 
absolute minimum the opportunity for bacteriological contamination. Public 
Health Service officials have recommended that “good housekeeping” 
procedures be followed, such as: regular inspections for concentrations 
of dirt, scale, and algae; periodic flushing and cleaning; and the following 
of a complete water treatment program including biocidal treatment.
The visual inspection should take place at least once a week during the 
operating  season.  The  periodic  flushing  and  cleaning  should  be  done 
before and after each cooling season, but in any event at least twice a 
year. The louvers, drift eliminators, easily accessible fill surfaces and the 
coil should be flushed by use of a moderate-pressure water nozzle, being 
careful not to cause physical damage. A reliable water treatment program 
should be installed and maintained. Filtration devices may be employed 
to reduce the suspended solids concentrations, thus increasing the ef-
fectiveness  of  the  water  treatment  program.  See  Fluid  Cooler  Startup 
instructions on page 13.
Blowdown:
A  fluid  cooler  cools  water  by  continuously  causing  a  portion  of  it  to 
evaporate. Although the water lost by evaporation is replenished by the 
makeup  system,  it  exits  the  tower  as  pure  water—leaving  behind  its 
burden of dissolved solids to concentrate in the remaining water. Given 
no means of control, this increasing concentration of contaminants can 
reach a very high level.
In order to achieve water quality which is acceptable to the fluid cooler,  the 
selected water treatment company must work from a relatively constant 
level of concentrations. This stabilization of contaminant concentrations 
is usually accomplished by blowdown, which is the constant discharge 
of a portion of the circulating water to waste. As a rule, acceptable levels 
on which to base a treatment schedule will be in the range of 2-4 con-
centrations. The following table shows the minimum amount of blowdown 
Maintenance
 Warning