Fluid Cooler Maintenance
Some maintenance procedures may require maintenance personnel to 
enter the fluid cooler. Each cased face of the fluid cooler has a door for 
access to the interior of the tower. 
The  optional  fan  deck  ladder—models  MHF706  and  MHF707—  is  de-
signed and intended solely for  personnel to gain access to the fan deck. 
The fan deck ladder should not be used to enter or exit the  access doors 
located on the cased face of the tower unless the optional access door 
platform is provided.
The purchaser or owner is responsible for providing a safe method 
for entering or exiting the access door. Use of the fan deck ladder to
enter or exit the access doors may result in a fall.
Included with this instruction packet are separate User Manuals on each 
major operating component of the tower, and it is recommended that you 
read them thoroughly. Where discrepancies may exist, the separate User 
Manuals will take precedence.
The following is recommended as a minimum routine of scheduled main-
tenance:
Always  shut  off  electrical  power  to  the  tower  fan  motor  prior  to 
performing any inspections that may involve physical contact with 
the mechanical or electrical equipment in or on the tower. Lock out
and tag out any electrical switches to prevent others from turning 
the power back on. Service personnel must wear proper personal
protective clothing and equipment.
Maintenance
 Warning
Bushing Fastener  
Torque Values
 Warning
Bushing
Fastener
Torque  ft·lb
ƒ
SH
1
4
 - 20
6
SDS
1
4
 - 20
6
SD
1
4
 - 20
6
SK
5
16
 - 18
13
SF
3
8
 - 16
22
E
1
2
 - 13
35
F
9
16
 - 12
65