has remained effective. Unless there is evidence of a generalized failure 
of the galvanizing, localized touch-up should be all that is required.
To the extent that the galvanizing (zinc coating) still exists, paint will
not adhere to it readily. Contact the manufacturer of the coating you 
intend to use for instructions.
Fluid cooler framework: Check structural bolted connections and tighten 
as required.
Fans: Check fan assembly bolting and tighten as required. Use torque 
values prescribed in the Fan User Manual.
Fans shaft bearings: If equipped, lubricate fan shaft bearings at close of 
each operating season—see page 26.
Electric motors: Clean and lubricate motor at close of each operating 
season (refer to motor manufacturer’s recommendations.) Check motor 
anchor bolts and tighten as required. See Page 28 for fluid coolers with 
motor located outside the plenum option.
Do not start motor before determining that there will be no interfer-
ence with free rotation of the fan drive.
The motor(s) should be operated for three hours at least once a month. 
This serves to dry out windings and re-lubricate bearing surfaces (refer 
to the Marley 
“Electric Motor User Manual” Manual 92-1475 available 
at spxcooling.com.
At  start  of  new  operating  season,  make  sure  bearings  are  adequately 
lubricated before returning motor to service.
Prolonged Shutdown
If  shutdown  period  is  longer  than  seasonal,  contact  your  Marley  sales 
representative for additional information.