7
Hoisting clips are provided for ease of unloading and positioning the 
fluid cooler. For overhead lifts or where additional safety is required,
safety slings should also be placed under the fluid cooler modules. 
Under no circumstances should you combine the top and bottom 
modules of modular  models and attempt to hoist them at the same 
time by utilizing the hoisting clips alone!
Fluid Cooler installation
These installation instructions are intended to help you prepare be-
fore your fluid cooler arrives. If discrepancies exist between these
instructions and those shipped with the fluid cooler, the instructions 
shipped with the fluid cooler will govern.
1.   Prior  to  placement  of  the  fluid  cooler,  confirm  that  the  supporting 
platform is level, and that the anchor bolt holes are correctly located 
in accordance with Marley drawings. 
2.   Place bottom module on your prepared supports, aligning anchor bolt 
holes with those in your supporting steel. Make sure that the orientation 
agrees with your intended piping arrangement. Attach fluid cooler to 
supporting steel with 
3
4
" diameter bolts and flat washers (by others). 
See support drawing for location and quantity. Position flat washers 
between the bolt head and the fluid cooler basin flange.
3.   Before  setting  top  module  in  place  on  bottom  module,  clean  any 
debris from the underside of the top module fill, skid and beams and 
from the top of the bottom module and remove shipping cover from 
bottom of top module—replace fasteners at side of module to pre-
vent leaks. Place top module on the top peripheral bearing surface 
(factory-installed gasket) of bottom module, aligning mating holes as 
it is set in place. Attach top module to bottom module with fasteners 
provided according to drawings shipped with your fluid cooler.
4.   Connect the recirculation piping with rubber boot shipped with the 
bottom module piping according to drawings shipped with you fluid 
cooler.
5.   Attach makeup water supply piping to appropriately-sized float valve 
connection located in collection water basin side wall. Install the drain 
and overflow according to drawings shipped with your fluid cooler. 
If you wish to pipe overflow and drain water to a remote discharge 
point, make those connections at this time also.
Note
Installation
 Warning