Caterpillar Portable Generator UL 2200 Manual De Usuario

Descargar
Página de 6
®
5
RATING DEFINITIONS AND CONDITIONS
S T A N D B Y   5 0 0   e k W   6 2 5   k V A
6 0   H z     1 8 0 0   r p m     4 8 0   V o l t s
Meets or Exceeds International Specifications: · ABGSM TM3,
AS1359, AS2789, BS4999, BS5000, BS5514, DIN6271, DIN6280,
EGSA101P, IEC34/1, ISO3046/1, ISO8528, JEM1359, NEMA MG
1-22, VDE0530, 89/392/EEC, 89/336/EEC
Standby - Output available with varying load for the duration of
the interruption of the normal source power.  Standby power in
accordance with ISO8528.  Fuel stop power in accordance with
ISO3046/1, AS2789, DIN6271, and BS5514.  Standby ambients
shown indicate ambient temperature at 100 percent load which
results in a coolant top tank temperature just below the shut-
down temperature.
Ratings are based on SAE J1349 standard conditions. These
ratings also apply at ISO3046/1, DIN6271, and BS5514 standard
conditions.
Fuel rates are based on fuel oil of 35º API [16º C (60º F)] gravity
having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when used at 29º
C (85º F) and weighing 838.9 g/liter (7.001 lbs/U.S. gal.).
Additional ratings may be available for specific customer
requirements. Consult your Caterpillar representative for
details.
17 April 2002        10:34 AM