HONEYWELL AM (HAM) 0-10VDC MODULE INSTALLATION INSTRUCTIONS
P/N# 240005544, Rev. 1.1 [04/06] • Printed in USA • Made In USA
GAS FIRED DIRECT VENT MODULATING HOT WATER BOILER
INSTALLATION PROCEDURE
WARNING
Electrical shock hazard — Turn off power to the 
boiler  before  proceeding  with  the  installation. 
Failure to comply could result in severe personal 
injury, death, or substantial property damage.
MOUNTING AND WIRING THE HAM MODULE
– KIT COMPONENTS –
HAM Module with cable clamp and screws
Ribbon Cable
(2) 6 x ½” Hex Head Screws
– TOOLS REQUIRED –
Phillips-head screwdriver
Flat-head screwdriver
Small flat-head screwdriver
¼” nut driver
Drill and 
3
/
32
” drill bit
1.  Remove  boiler  front  jacket  panel  by  pulling  panel 
away from boiler.
2. Insert a small flat-blade screwdriver into slot on bot-
tom of HAM Module (at tapered end of module cover) 
and gently pry off the cover.
3. With HAM cover removed, carefully insert either end 
of the ribbon cable into the HAM plug. Cable will fit into 
the cutout on the end of the module cover and base. 
(See Figure 1.)
4. Route multiple boiler controller wires and alarm wires 
through the boiler cable ways, along with the other wir-
ing.  Strip  ends  and  attach  to  the  terminals  shown  in 
Figure 2. Use the cable clamp supplied in the HAM kit 
to secure the alarm wires to the module.
5. Mount HAM Module to right jacket or surface exte-
riour of boiler.
6. Fasten HAM cover on the module.
7. Plug the end of the ribbon cable into the empty sock-
et on the left end of the boiler control module.
8. Restore power to the boiler.
Cover
Figure 1 - HAM Module Assembly
Ribbon Cable
Base and
PC Board
Assembly
Figure 2 - HAM Wiring Connections
Alarm
Terminals
0-10vdc signal from multiple 
boiler control
(+)
(–)
Ribbon 
Cable