HONEYWELL AM (HAM) 0-10VDC MODULE INSTALLATION INSTRUCTIONS
P/N# 240005544, Rev. 1.1 [04/06] • Printed in USA • Made In USA
GAS FIRED DIRECT VENT MODULATING HOT WATER BOILER
INSTALLATION PROCEDURE
WARNING
Electrical shock hazard — Turn off power to the
boiler before proceeding with the installation.
Failure to comply could result in severe personal
injury, death, or substantial property damage.
MOUNTING AND WIRING THE HAM MODULE
– KIT COMPONENTS –
HAM Module with cable clamp and screws
Ribbon Cable
(2) 6 x ½” Hex Head Screws
– TOOLS REQUIRED –
Phillips-head screwdriver
Flat-head screwdriver
Small flat-head screwdriver
¼” nut driver
Drill and
3
/
32
” drill bit
1. Remove boiler front jacket panel by pulling panel
away from boiler.
•
•
•
•
•
•
•
•
2. Insert a small flat-blade screwdriver into slot on bot-
tom of HAM Module (at tapered end of module cover)
and gently pry off the cover.
3. With HAM cover removed, carefully insert either end
of the ribbon cable into the HAM plug. Cable will fit into
the cutout on the end of the module cover and base.
(See Figure 1.)
4. Route multiple boiler controller wires and alarm wires
through the boiler cable ways, along with the other wir-
ing. Strip ends and attach to the terminals shown in
Figure 2. Use the cable clamp supplied in the HAM kit
to secure the alarm wires to the module.
5. Mount HAM Module to right jacket or surface exte-
riour of boiler.
6. Fasten HAM cover on the module.
7. Plug the end of the ribbon cable into the empty sock-
et on the left end of the boiler control module.
8. Restore power to the boiler.
Cover
Figure 1 - HAM Module Assembly
Ribbon Cable
Base and
PC Board
Assembly
Figure 2 - HAM Wiring Connections
Alarm
Terminals
0-10vdc signal from multiple
boiler control
(+)
(–)
Ribbon
Cable