Siemens Remote Displays SITRANS RD100 Manual De Usuario
7ML19985JU01
SITRANS RD100 – INSTRUCTION MANUAL
Page 3
Calibration
• Two-step; non-interacting low and high
Calibration Range
• 4 mA input: display of -1000 to +1000 counts
• 20 mA input: display of 4 mA count value +20 to 2000 counts, to a max. display of
• 20 mA input: display of 4 mA count value +20 to 2000 counts, to a max. display of
1999 counts
Accuracy
• ±0.1% of span ±1 count
Conversion Rate
• 2.5 conversions per second
Approvals
• Intrinsically Safe:
• FM/CSA Class I, II, III, Division 1, Groups A to G T4
• FM/CSA Class I, Zone 0, Group IIC
• FM/CSA Class I, Zone 0, Group IIC
• Non-incendive:
• FM/CSA Class I, Division 2, Groups A to D
• FM/CSA Class II and III, Division 2, Groups F and G
• FM/CSA Class II and III, Division 2, Groups F and G
See "RD100 Remote Display - Approval Connections Control Drawing" shipped with the
unit and located on the Instruction Manual CD, for complete Intrinsically Safe installation
instructions.
unit and located on the Instruction Manual CD, for complete Intrinsically Safe installation
instructions.