Rate Time-Base: 
 
This step is for programming time-base for calculation of Rate. Units of time-base are seconds. Again, the 
active digit will be flashing. To change the value, push ^v key. To activate another digit for change, use 
<NXT> key. On finishing, push SETUP key. 
 
Remote Tare/Hold: 
 
Remote Tare/Hold feature lets you select between the remote switch being used for resetting tare or holding 
the reading on the display. The display will read 'RT TARE' (for remote Tare) or 'RT HOLD' ( for remote 
display hold feature ). To get the alternate mode push ^v key. Else push SETUP key and this will get you 
into the next function.  
 
Input Type: 
 
The step after remote Tare/Hold is selecting the input type. The display will first read ‘IP  TYPE’ followed 
by  the current selection. Various input types are: 
 
  i)    CURRENT  4-20MA Signal 
  ii)   VOLTAGE  0-10Vdc, 0-5Vdc etc. 
  iii)  LO  VOLT  0-100mv etc. 
 
To make a selection push ^v key. After selection push SETUP key to go to the next  step. 
 
Input Range: 
 
The following step is the last step in this process. This is where you program the input range of your signal.  
On entering this mode, the display will first read "IP  RNGE" (for input range) followed by the indication 
of current input range. Following RANGE values should be entered for various inputs: 
 
  INPUT TYPE  INPUT RANGE  PROGRAMMED VALUE 
 
  VOLTAGE   0-10VDC Signal   10.000   
 VOLTAGE   0-5VDC Signal   5.000  
  CURRENT   4-20ma Loop Current   20.00  
  LO VOLT   0-100 Millivolt Signal   100.0  
 
If the end user recalibrates any of the process inputs to different values he/she must enter new values here. 
 
 
NOTE:  THE INPUT TYPE IS SET ACCORDING TO THE MODEL ORDERED. SIMPLY MAKING A 
SELECTION WILL NOT CONVERT THE UNIT FROM A CURRENT TO A VOLTAGE OR A 
MILLIVOLT UNIT. THIS IS A HARDWARE CHANGE AND MUST BE SELECTED AT THE TIME 
OF PLACING THE ORDER. 
 
 
After entering the desired input range, push the SETUP key. This will take us back to the very beginning of  
setup mode with the display reading SETUP briefly and then SCALING. To exit at this point push and hold 
RESET key till the display shows ‘SAVING’