FieldServer FS-8704-06 Manual De Usuario
FS-8704-06 BACnet IP Driver Manual
Page 6 of 24
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
4.2.
Client Side Connection Descriptions
Section Title
Adapter
Column Title
Function
Legal Values
Adapter
Adapter Name
N1, N2
4
Protocol
Specify protocol used
BACnet_IP
Poll_Delay*
Time between internal polls
0-32000s; 0.25s
IP_Port*
Specify the UDP port that will be used to
communicate with other BACnet Client devices.
communicate with other BACnet Client devices.
Any legal IP port value
(1 - 65535); 47808
(1 - 65535); 47808
Example
// Client Side Connections
Connections
Adapter,
Protocol,
Poll_Delay
N1,
Bacnet_IP,
0.500s
4.3.
Client Side Node Descriptors
Section Title
Nodes
Column Title
Column Title
Function
Legal Values
Node_Name
Provide name for Node
Up to 32 alphanumeric
characters
characters
Node_ID
BACnet station address of physical Server
node
node
1 - 4194303
Protocol
Specify protocol used
BACnet_IP
Adapter
Specify port Adapter used
N1, N2
4
Example
// Client Side Nodes
Nodes
Node_Name,
Node_ID,
Protocol,
Adapter
BCU_01,
1,
Bacnet_IP,
N1
4
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.