FieldServer FS-8704-06 Manual De Usuario

Descargar
Página de 24
FS-8704-06 BACnet IP Driver Manual 
 
 
 
 
 
Page 6 of 24 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
4.2. 
Client Side Connection Descriptions 
Section Title 
Adapter 
Column Title 
Function 
Legal Values 
Adapter 
Adapter Name 
N1, N2
4
 
Protocol 
Specify protocol used 
BACnet_IP 
Poll_Delay* 
Time between internal polls 
0-32000s; 0.25s 
IP_Port* 
Specify the UDP port that will be used to 
communicate with other BACnet Client devices. 
Any legal IP port value 
(1 - 65535); 47808  
 
Example 
 
//    Client Side Connections 
 
 
 
Connections 
 
 
Adapter, 
Protocol, 
Poll_Delay 
N1, 
Bacnet_IP, 
0.500s 
 
4.3. 
Client Side Node Descriptors 
Section Title 
Nodes 
Column Title 
Function 
Legal Values 
Node_Name 
Provide name for Node 
Up to 32 alphanumeric 
characters 
Node_ID 
BACnet station address of physical Server 
node 
1 - 4194303 
Protocol 
Specify protocol used 
BACnet_IP 
Adapter 
Specify port Adapter used 
N1, N2
4
 
 
Example 
 
//    Client Side Nodes 
 
 
 
 
Nodes 
 
 
 
Node_Name, 
Node_ID, 
Protocol, 
Adapter 
BCU_01, 
1, 
Bacnet_IP, 
N1 
 
                                                 
4
  Not  all  ports  shown  are  necessarily  supported  by  the  hardware.  Consult  the  appropriate  Instruction 
manual for details of the ports available on specific hardware.