CAT Titan 250 Manual De Usuario

Descargar
Página de 81
Turbomachinery Package Specification 
Titan 
250 Generator Set 
On detection of a fire by the optional fire and gas detection system, the fire control panel 
activates the fire suppression system release solenoids located on the water mist 
suppression skid. On receipt of this signal, the solenoid actuated control heads activate 
the discharge valves on the water cylinders, releasing a water mist into the enclosure. A 
pressure switch in the water mist discharge piping transmits an electrical signal to the fire 
control panel to activate a release solenoid to close pressure-operated dampers on all 
vent openings. The water mist nitrogen actuator valve is also provided with a manual 
release lever. 
11.3.11 Fire Cylinder Cabinets 
When installed outdoors, weatherproof fire cylinder cabinets are available to house the 
extinguishing agent. The cabinets are equipped with service doors. The manual pull 
levers are routed by cable to the exterior wall of the cabinet. 
 
 
Figure 23.  Typical CO
Fire Suppression Cylinders and Cabinets 
 
 
 
Figure 24.  Typical Water Mist Fire Suppression Cylinders and Cabinet 
© 2008 Solar Turbines Incorporated. All rights reserved. 
TPS250GS/908 - Preliminary 
49