Power
 
 
ProLiant DL160 G6 Fully Configured
115V/60Hz
220V/50Hz
Fully Loaded System Input Wattage (W)
448
445
Fully Loaded System Input Current (A rms)
3.833
2.046
Fully Loaded System Thermal (BTU- Hr)
1529
1518
Fully Loaded System VA (Volt-Amp)
449
454
System Inrush Current with all power supplies loaded (A)
10.1
10.96
Power cord requirements
Nema 5-15P to IEC320-C13
IEC320-C13 to IEC320-C14
NOTE: Power shown is for a fully configured system consisting of (2) CPU, (8) double-sided DIMMs, (2) HDDs, (1) CD-ROM, and (2) PCI
cards.
Power Cord
AF556A
 
Server Power Cords
One 6' Highline (IEC-IEC) power cord ships standard
NOTE: HP ProLiant DL servers no longer ship standard with NEMA power cords (163719-002) that allow
connection to 110V US wall outlets in a home or office. ProLiant DL servers are primarily connected to
PDU's in data center racks so they now ship standard with only a PDU power cord (416151-B21). If a user
wishes to power a ProLiant DL server using a 110V receptacle (NEMA-15), the NEMA power cord must be
ordered separately.
If customers require a local power cord, they can check the power cord matrix for the appropriate cord.
Please see the following power cord matrix: 