9700 SERIES UPS 
OWNERS / TECHNICAL MANUAL 
Page Number: 
v
 
MITSUBISHI ELECTRIC 9700SERIES UPS   
 
WARNING  2 
 
This UPS does not include a Bypass Input circuit breaker (MCCB).    The 
Bypass Input contactor (CB3) does not protect against load induced 
short circuits.    The bypass input circuit breaker (MCCB) is field supplied 
and installed.    Breaker(MCCB)'s Specifications are as follows: 
 
Capacity (kVA)  Bypass Voltage (VAC) Maximum Bypass 
Rating (AAC) 
Recommended 
Breaker (A) 
100 208  278 350 
100 480  120 150 
100 600 
96 100 
150 208  416 500 
150 480  180 225 
150 600  144 150 
225 208  625 700 
225 480  271 300 
225 600  217 225 
300 480  361 400 
300 600  289 300 
375 480  451 500 
375 600  361 400