Brocade Communications Systems 53-1002580-01 Manual De Usuario

Descargar
Página de 82
Brocade 6910 Ethernet Access Switch Hardware Installation Guide
15
53-1002580-01
Connecting to a Power Source
2
Connecting DC Power
When using 20-60Vdc power, an external DC power supply must be connected to the DC power 
connector on the left side of the front panel. DC input (DC source) must be isolated from AC mains 
by reinforced insulation.
DANGER
Remove both power cords before servicing.
NOTE
To provide adequate circuit protection between the DC power supply and the switch, all intermediate 
wiring and circuitry should be rated to carry a load at least two times the maximum rating for this 
switch (see 
NOTE
For a DC system, use a grounding wire of at least 18 American Wire Gauge (AWG). The 18 AWG wire 
should be attached to an agency-approved crimp connector (provided on the chassis), and crimped 
with the proper tool. The crimp connector should allow for securement to a ground screw on the 
enclosure.
NOTE
Wiring for the power input terminals on the switch are described below. Wiring of the DC power 
supply terminals depends on the equipment in use on the local site, but should be wired in such a 
way as to meet the input requirements shown in 
 on page 16. The wiring 
should also be color coded according to local standards to ensure that the input power and ground 
lines can be easily distinguished.
To connect the switch to a power source:
1. First verify that the DC power can provide 20-60Vdc, 1.9A.
2. Prepare two wires for each power source to be used. Use 18 AWG stranded copper wire. Make 
sure these wires are not plugged into the power source.
3. Use a wire stripper to carefully strip about a half an inch of the outer insulation off the end of 
each wire, exposing the copper core.
4. Twist the copper wire strands together to form a tight braid. If possible, solder the exposed 
braid of wire together for better conductivity.
5. Connect the external power feed and power ground/return lines to the DC plug (provided with 
the switch) as shown in the following figure. The plugs are labeled on the front of the chassis, 
above the DC power connection block. The -48 VDC power feed uses the “-48VDC” input lines. 
Use a small flat-tip screwdriver to loosen the screws on the power plug and open the wire 
clamps.
This equipment installation must meet NEC/CEC code requirements. Consult local authorities for 
regulations.