Bradford-White Corp BRUTE DELUXE BMT2V Manual De Usuario

Descargar
Página de 44
 
B
raDforD
 W
hite
 C
orp.
Page 30
control switches this 24V from the input terminal to 
the stage terminal. The input for stage 1 is initiated 
by closing the circuit between the 2 terminals on the 
terminal strip labeled "input stage 1." The input for 
stage 2 is initiated by closing the circuit between the 2 
terminals on the terminal strip labeled "input stage 2."
6.4  Sequence of Operation
The pump time delay relay will receive a signal 
to initiate. If the unit is pump-mounted, the pump 
will be energized. The pump terminals on the field-
wiring terminals strip will energize a field pump that is 
properly interlocked with the Brute Deluxe.
Once the water flow switch makes, if all of the 
safety interlocks are closed, the ignition  module will 
energize the blower(s) for a 15-second pre-purge, 
followed by a 40-second period to allow the ignitor to 
heat.
The ignition control energizes the blower. The 
blower pressurizes the air box (which supplies air to 
the burners) and closes the normally-open contact 
on the airflow pressure switch. The blocked vent 
pressure switch senses the pressure in the exhaust 
plenum. This switch opens if the pressure is excessive 
(as an indicator of a blocked vent). When these two 
pressure switches are closed, voltage is sent to the 
PSW terminal on the ignition control, which allows the 
ignition module to proceed with the ignition sequence.
If the airflow proving circuit is not proven, 
ignition module will lock out. 
Section 6.5 
describes 
the result of air flow faults in more detail.
When the ignition control gets the signal at the 
PSW terminal, it will energize its MV terminal, which 
sends power to the stage one (or on/off) main valve.
After a 7-second trial for ignition, the ignitor 
switches to flame sense mode. If a flame is not 
detected, the gas valve will close and the ignition 
module will attempt ignition again (up to two more 
times, for a total of three attempts.) If all three 
attempts fail, the ignition control will lock out.
If flame is sensed, the burner will continue to 
fire as long as there is a call for heat, and none of the 
safety circuit is interrupted.
If there is a call for stage 2 on a 2-stage unit, that 
valve will be energized.
If there is a loss of flame signal during a 
successful firing sequence, the ignition control will 
remove power from the gas valves, and then attempt 
to light up to two more times. If successful, the Brute 
Deluxe will fire normally. If unsuccessful, the ignition 
control will lock out.
When the call for heat is satisfied, the gas 
valve(s) closes, and the blower starts a 45 second post-
purge. Any pump connected to the Brute Deluxe pump 
time delay relay will continue to run for the time delay 
period (dialed by the user, 0.1 to 10 minutes).
6.5 Ignition Control Reaction to Air Flow / 
Blocked Vent Pressure Switch
Air flow and blocked vent status are continuously 
monitored by the Brute Deluxe ignition control, at the 
control’s PSW terminal.
At the start of an ignition sequence, if the ignition 
control sees power at PSW for 30 seconds, but the 
combustion blower has not yet been energized by the 
control (F1 and F2).  The ignition control will remain 
in this fault mode, with the blower off. If the power to 
PSW is removed while there is still a call for heat, the 
ignition sequence will start again, but the main valves 
will not be energized until PSW sees power during the 
ignition sequence.
At the start of an ignition sequence, the control 
sends the combustion blower output (F1 and F2). If 
the control does not see power at PSW for more than 
30 seconds, the control will remain in this fault mode, 
with the blower on. If proper airflow is later detected 
on PSW, the control begins a pre-purge and a normal 
trial for ignition.
If the PSW signal is lost while the Brute Deluxe 
is firing, the control will immediately de-energize the 
gas valve terminal (MV). The blower will remain on 
for the post-purge period (45 seconds), and the control 
will continue to monitor the PSW input. If the signal 
is detected during the post-purge period, a normal trial 
for ignition will begin, starting with the 15-second 
pre-purge. If the signal is not detected during the post-
purge, the control will lockout with the blower off.
*1 Difference between the temperatures at which the two switches
make R-W. Adjustable from 3°F to 10°F (1.7°C to 5.6°C) on standard
models, or from 3.6°F to 12°F (2.0°C to 6.7°C); 55°F to 175°F (13°C
to 79°C) models.
*2 Two DPDT switches operate in sequence. Each switch
differential is fixed at approximately 3°F (1.7°C) on standard models,
or 3.6°F (2.0°C); 55°F to 175°F (13°C to 79°C) models.
Figure 19. Honeywell L8008G.