Bradley Smoker Bradley Technologies Inc. Plumbing Product S19-220PT Manual De Usuario

Descargar
Página de 5
Installation
S19-220PT, S19-220BPT
Installation
Instructions
NOTE:  Flush the water
supply line before beginning
installation.
Supplies Required:
• (3) 3/8" wall fasteners
and bolts
• Pipe sealant
• Piping to 1/2" IPS water
supply inlet on unit
•  Sign-mounting hardware
Step 1: Install inlet
drain fittings
NOTE: Top of eyewash heads
should be 33"-45" (838mm-
1142mm) from floor.
1. Position the inlet drain
fitting over the 1-1/4"
drain outlet pipe from
wall. 
2. Using the inlet drain
fitting as a template,
mark the bolt hole
locations on wall OR
install three suitable
fasteners (supplied by
installer) for 3/8" bolts
in the wall at the
marked hole locations
(see Figure 1).
3. Bolt the inlet drain
fitting to the wall or
wall fasteners using
3/8" bolts (supplied by
installer).
Step 2: Assemble eyewash 
1. Assemble eyewash components as shown in Figure 2 on page 4.
• Apply pipe sealant (supplied by installer) to all male-threaded pipe joints.
• Use a strap wrench around pipes when tightening to prevent marring.
Step 3: Connect water supply
1. Connect the water supply piping (supplied by installer) to the 1/2" IPS inlet on the eyewash. 
2. Connect the P-trap and the tailpiece to the 1-1/4 IPS drain outlet on the eyewash.
3. Mount the safety sign to a wall or pipe using sign-mounting hardware (supplied by installer).
4. Open the water supply lines. Test for leaks and adequate water flow.
Ø10"
(254mm)
13-1/4"
(337mm)
8-1/4"
(210mm)
Ø10-3/4"
(273mm)
13-5/8"
(346mm)
8-1/4"
(210mm)
8-3/4"
(222mm)
4-1/2"
(114mm)
30-1/2" (775mm)
Suggested 
Height
To Floor
36" (914mm)
Suggested 
Height
To Floor
13"
(330mm)
S19-220PT
S19-220BPT
S19-220PT
S19-220BPT
15-1/2"
(394mm)
7-3/8"
(187mm)
5-1/4"
133mm)
2-1/4"
(57mm)
5/16"
(8mm)
MTG.
HOLE
4"
(102mm)
4"
(102mm)
15-7/8"
(403mm)
7-3/8"
(187mm)
5-1/4"
133mm)
2-1/4"
(57mm)
5/16"
(8mm)
MTG.
HOLE
4"
(102mm)
4"
(102mm)
Figure 1
3
Bradley Corporation • 215-1251 Rev. B; EN 06-532G
4/30/07