Bosch Appliances Home Security System APC-AMC2-4WCF Manual De Usuario
42 en | Installing
AMC2 4W
F.01U.024.965 | V.4 | 2006.09
Installation manual
Bosch Security Systems
Fig. 5.19
Wet mode and dry mode of the AMC2 4W relay outputs
For the protection of damage the relay keep in mind, that ...
–
the maximum switching current is 1,25A
–
the maximum switching voltage is 30V DC
–
ohm resistive load can be connected to the relay, only
–
inductive loads have to be short circuited using recovery
diodes - see: Figure 5.20. These diodes (BAX12A) are sup-
plied with every AMC2 4W package.
–
If you need higher voltage for special constructions you
can connect external relays to the outputs. Recommended,
depending on the power supply mode, are the relay types
of the company Wieland:
•
Flare move 12DC1W10A
•
Flare move 24DC1W16A
But you can also use products of manufacturer in your
country - take care that the values of the product are iden-
tical with the products listened above.
!
WARNING!
Keep in mind the following specifications.